6. Minimum and maximum water flow rates
A low flow rate will not only compromise the performance of the unit but also increase the water temperature difference be-
tween the periods when the unit is in operation and when the unit is stopped. A high flow rate will cause the pipes to corrode.
Adjust the circulating flow rate so that the difference between the inlet and outlet temperatures will be between 3 ºC and 10
ºC. Refer to the table below for the standard, minimum, and maximum flow rates.
The hot water flow rate will be considered appropriate if the difference between the inlet and outlet water temperatures is be-
tween 3 ºC and 10 ºC.
If the temperature difference is less than 3 ºC
Decrease the flow rate.
If the temperature difference is more than 10 ºC
Increase the flow rate. Check the pipes for air pockets, and make sure that the pump has enough capacity to sustain appro-
priate water pressure in a given water circuit.
7. Maintaining the appropriate amount of water in the water circuit.
(1) Amount of water in the water circuit
Shortage of water in the circulating water circuit may shorten the operation time of the unit or cause large fluctuations of water
temperature. The table below shows the minimum allowable amount of water in the water circuit. If the piping length is too
short to secure this amount, install a cushion tank to ensure that the circuit has enough water in it.
(2) Calculating the amount of water in the circuit
The amount of water in the circuit can be obtained using the following formula.
Amount of water in the water circuit = Amount of water in the water Amount of water in the unit + and Amount of water
in the load-side or heat source unit
The table below shows the amount of water in the water piping per 1 m
Amount of water in the piping
The table below shows the amount of water in the unit.
Amount of water in the unit
8. Sizes and the material types of the pipes on the unit
The table below shows the sizes of the pipes.
Pipe sizes
Standard, Minimum, and Maximum flow rates
Unit: m
3
/h
CRHV-P600YA-HPB
Standard flow rate (50Hz)
Minimum allowable flow
rate
Maximum allowable flow
rate
Heating
Hot water side
10.3
3.2
15.0
Heat source side
14.7
4.5 (counter flow)
16.0
2.0 (parallel flow)
Model
Minimum allowable amount of hot water (
ℓ
)
Minimum allowable amount of heat source (
ℓ
)
CRHV-P600YA-HPB
550
390
Pipe size
3/4B (20A)
1B (25A)
1 1/4B (32A) 1 1/2B A(40A)
2B (50A)
1 1/2B (65A)
Internal volume per meter (
ℓ
/m)
0.37
0.60
0.99
1.36
2.20
3.62
Model
Hot water side (
ℓ
)
Heat source side (
ℓ
)
CRHV-P600YA-HPB
15
10
Model
Hot water side
Heat source side
CRHV-P600YA-HPB
R2 male thread pipe <SUS304>
R2 male thread pipe <SUS304>
Содержание CRHV-P600YA-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE1312A GB ...
Страница 9: ... 2 HWE1312A GB ...
Страница 19: ... 12 HWE1312A GB ...
Страница 41: ... II Restrictions 34 HWE1312A GB ...
Страница 43: ... 36 HWE1312A GB ...
Страница 51: ... III Unit Components 44 HWE1312A GB ...
Страница 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Страница 53: ... 46 HWE1312A GB ...
Страница 61: ... IV Remote Controller 54 HWE1312A GB ...
Страница 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Страница 63: ... 56 HWE1312A GB ...
Страница 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Страница 68: ... 61 HWE1312A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 63 2 Principal Parts and Functions 64 ...
Страница 69: ... 62 HWE1312A GB ...
Страница 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Страница 75: ... 68 HWE1312A GB ...
Страница 107: ... VII Control 100 HWE1312A GB ...
Страница 109: ... 102 HWE1312A GB ...
Страница 117: ... 110 HWE1312A GB ...
Страница 165: ... IX Troubleshooting 158 HWE1312A GB ...
Страница 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Страница 167: ... 160 HWE1312A GB ...
Страница 170: ......