9. Additional refrigerant charge

At the time of shipping, the heat source unit is charged with the refrigerant.  As this
charge does not include the amount needed for extended piping, additional charg-
ing for each refrigerant line will be required on site.  In order that future servicing
may be properly provided, always keep a record of the size and length of each
refrigerant line and the amount of additional charge by writing it in the space pro-
vided on the heat source unit.

9.1. Calculation of additional refrigerant

charge

Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.

Use the table to the below as a guide to calculating the amount of additional
charging and charge the system accordingly.

If the calculation results in a fraction of less than 0.1 kg [4 oz], round up to the
next 0.1 kg [4 oz].  For example, if the result of the calculation was 10.62 kg
[373.3 oz], round the result up to 10.7 kg [376 oz].

<Additional Charge>

9.2. Precautions concerning piping connec-

tion and valve operation

Conduct piping connection and valve operation accurately.

Flange type side connecting pipe is assembled in factory before shipment.

1

For brazing to the connecting pipe with flange, remove the connecting pipe
with flange from the ball valve, and braze it outside of the unit.

2

During the time when removing the connecting pipe with flange, remove
the seal attached on the rear side of this sheet and paste it onto the flange
surface of the ball valve to prevent the entry of dust into the valve.

3

The refrigerant circuit is closed with a round, close-packed packing upon
shipment to prevent gas leak between flanges. As no operation can be
done under this state, be sure to replace the packing with the hollow pack-
ing attached at the piping connection.

4

At the mounting of the hollow packing, wipe off dust attached on the flange
sheet surface and the packing. Coat refrigerating machine oil (Ester oil,
ether oil or alkylbenzene [small amount]) onto both surfaces of the pack-
ing.

[Fig. 9.2.1] (P.3)

A

Close-packed packing

B

Hollow packing

After evacuation and refrigerant charge, ensure that the handle is fully open. If
operating with the valve closed, abnormal pressure will be imparted to the
high- or low-pressure side of the refrigerant circuit, giving damage to the com-
pressor, four-way valve, etc.

Determine the amount of additional refrigerant charge by using the formula,
and charge refrigerant additionally through the service port after completing
piping connection work.

After completing work, tighten the service port and cap securely not to gener-
ate gas leak.

Flare machining dimension for systems using R410A is larger than that for
systems using other types of refrigerant in order to increase the air tightness.

Refer to the table on the below for flare machining dimensions, and follow the
regulations set forth by the local authorities. Seal off the opening of the pipe
with a closure material (not supplied) to keep small animals from entering the
pipe if that is a concern.

flare machining dimension (mm)

<Example 1>
Indoor No. 1: 15 A: ø19.05 [3/4] 40 m [131 ft] a: ø6.35 [1/4] 10 m [32 ft]

No. 2: 72 B: ø9.52 [3/8] 10 m [32 ft] b: ø9.52 [3/8]

5 m [16 ft]

No. 3: 15

c: ø6.35 [1/4] 10 m [32 ft]

No. 4: 12

d: ø6.35 [1/4] 10 m [32 ft]

No. 5: 24

e: ø9.52 [3/8] 10 m [32 ft]

The total length of each liquid line is as follows:
ø19.05 [3/4]: A = 40 m [131ft]
ø9.52 [3/8]: B + b + e = 10 [32] + 5 [16] + 10 [32] = 25 m [80 ft]
ø6.35 [1/4]: a + c + d = 10 [32] + 10 [32] + 10 [32] = 30 m [96 ft]

Therefore,
<Calculation example>
Additional refrigerant charge

= 40 [131] 

×

 0.16 [1.72] + 25 [80] 

×

 0.06 [0.65]

+ 30 [96] 

×

 0.024 [0.26] + 2.0 [71oz] = 10.7 kg [376oz]

<Example 2>
Indoor No. 1: 08 A: ø19.05 [3/4] 40 m [131 ft] a: ø6.35 [1/4] 10 m [32 ft]

No. 2: 06 B: ø9.52 [3/8] 10 m [32 ft] b: ø6.35 [1/4]

5 m [16 ft]

No. 3: 12 C: ø12.7 [1/2] 10 m [32 ft] c: ø6.35 [1/4] 10 m [32 ft]
No. 4: 12 D: ø9.52 [3/8] 10 m [32 ft] d: ø6.35 [1/4] 10 m [32 ft]
No. 5: 12

e: ø6.35 [1/4] 10 m [32 ft]

No. 6: 72

f: ø9.52 [3/8] 10 m [32 ft]

No. 7: 06

g: ø6.35 [1/4]

5 m [16 ft]

The total length of each liquid line is as follows:
ø19.05 [3/4]: A = 40 m [131 ft]
ø12.7 [1/2]: C = 10 m [32 ft]
ø9.52 [3/8]: B + D + f = 10 [32] + 10 [32] + 10 [32] = 30 m [96 ft]
ø6.35 [1/4]: a + b + c + d + e + g = 10 [32] + 5 [16] + 10 [32] + 10 [32] + 10 [32] +

5 [16] = 50 m [160 ft]

Therefore,
<Calculation example>
Additional refrigerant charge

= 40 [131] 

×

 0.16 [1.72] + 10 [32] 

×

 0.12 [1.29] + 30 [96] 

×

 0.06 [0.65] +

50 [160] 

×

 0.024 [0.26] + 2.5 [89] + 2.0 [71] = 15.1 kg [531 oz]

Value of  

α

1

Total capacity of connecting indoor units

α 

1

to Model 30

1.0 kg [36 oz]

Models 31 to 60

1.5 kg [53 oz]

Models 61 to 126

2.0 kg [71 oz]

Models 127 to 180

2.5 kg [89 oz]

Value of  

α

2

α 

2

BC controller (standard, main only)

0 kg [0 oz]

BC controller (sub) connected (one)

1.0 kg [36 oz]

BC controller (sub) connected (two)

2.0 kg [71 oz]

[Fig. 9.2.2] (P.3)

<A> [Ball valve (Low press. side/flanged type)]

<B> [Ball valve (High press. side/flared type)]

<C> This figure shows the valve in the fully open state.

A

Valve stem
[Fully closed at the factory, when connecting the piping, when evacuating, and
when charging additional refrigerant. Open fully after the operations above are
completed.]

B

Stopper pin [Prevents the valve stem from turning 90

°

 or more.]

C

Packing (Accessory)
[Manufacturer: Nichiasu corporation]
[Type: T/#1991-NF]

D

Connecting pipe (Accessory)
[Use packing and securely install this pipe to the valve flange so that gas leakage
will not occur. (Tightening torque:40 N·m [400 kg·cm]) Coat both surfaces of the
packing with refrigerating machine oil. (Ester oil, ether oil or alkylbenzene [small
amount])]

E

Open (Operate slowly)

F

Cap, copper packing
[Remove the cap and operate the valve stem. Always reinstall the cap after opera-
tion is completed. (Valve stem cap tightening torque: 23 ~ 27 N·m [230 ~ 270 kg·cm])]

At the
conditions
below:

flare nut size (mm)

A

B

outer diameter

ø6.35

ø9.52

ø12.70

ø15.88

ø19.05

size in inches

1/4"

3/8"

1/2"

5/8"

3/4"

dimension A

R410A

9.1

13.2

16.6

19.7

24.0

outer diameter

ø6.35

ø9.52

ø12.70

ø15.88

ø19.05

size in inches

1/4"

3/8"

1/2"

5/8"

3/4"

dimension B

R410A

17.0

22.0

26.0

29.0

36.0

+

α

1 +

 α

2

=

+

+

+

Additional
refrigerant
charge

(kg) [oz]

High pressure
pipe size
Total length of
ø15.88 [5/8]

(m) 

×

 0.11 (kg/m)

(in) 

×

 1.18 (oz/ft)

High pressure
pipe size
Total length of
ø12.7 [1/2]

(m) 

×

 0.12 (kg/m)

(in) 

×

 1.29 (oz/ft)

High pressure
pipe size
Total length of
ø9.52 [3/8]

(m) 

×

 0.06 (kg/m)

(in) 

×

 0.65 (oz/ft)

High pressure
pipe size
Total length of
ø6.35 [1/4]

(m) 

×

 0.024 (kg/m)

(in) 

×

 0.26 (oz/ft)

High pressure
pipe size
Total length of
ø19.05 [3/4]

(m) 

×

 0.16 (kg/m)

(in) 

×

 1.72(oz/ft)

At the
conditions
below:

Содержание City Multi PQRY-P72TGMU-A

Страница 1: ...r safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte For use with R410A ...

Страница 2: ...4 ø14 9 16 Anchoring hole C Top view A Piping space for side piping B Heat source unit C Service space front side D Top view D Anti vibration pad etc E Concrete base E Piping space for top piping F Piping space for side piping G Heat source unit H Front view A Water circulation pipe B Close valve C Close valve D Water outlet A Short circuit wire Connected before delivery from manufacturer B Pump i...

Страница 3: ...ow press gas pipe ø19 05 3 4 ø22 2 7 8 ø28 58 1 1 8 B Unit mm in Î Total capacity of indoor units 54 55 72 Liquid line ø9 52 3 8 ø9 52 3 8 Ï Gas line ø15 88 5 8 ø19 05 3 4 A Unit mm in Å Heat source model P72 P96 ı High press side ø15 88 5 8 ø19 05 3 4 Ç Low press side ø19 05 3 4 ø22 2 7 8 Fig 9 2 2 9 2 9 Fig 9 2 1 A B 1 3 A Ball valve Low press side flanged type B Ball valve High press side flare...

Страница 4: ...rial C Lagging D Caulking material E Band F Waterproofing laye G Sleeve with edge H Lagging material I Mortar or other incombustible caulking J Incombustible heat insulation material A Power source B Transmission line C Ground screw D C C B B E F G H I J A LO HI LO HI B A K J L H M C D E N O F G I Fig 9 3 1 Fig 9 3 3 Fig 9 3 2 9 3 A A Nitrogen gas B To indoor unit C System analyzer D Lo knob E Hi ...

Страница 5: ... BC M1M2S 52 BS M1M2S 55 BC M1M2S 54 M1M2S System controller L3 L 6 L4 L 5 r 2 r 4 r 1 A B A B A B A B CN40 CN40 A B C E D M1M2 M1M2S TB7 TB3 IC 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 MA MA MA OC M1M2 M1M2S TB7 TB3 CN40 53 OC c 1 c4 c 3 BC M1M2S 52 BS M...

Страница 6: ...installing the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heater stove oven or other heat source it may generate noxious gases Do not reconstruct or ch...

Страница 7: ...nt If the conventional refrigerant and refrigerator oil are mixed in the R410A the refrigerant may deteriorated If water is mixed in the R410A the refrigerator oil may deteriorate Since R410A does not contain any chlorine gas leak detectors for conven tional refrigerants will not react to it Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate Be especi...

Страница 8: ...excess air Compressed water may form in the low temperature sections of heat source unit Use a drainage pipe connected to the drain valve at the base of the unit to drain the water There is a water vent plug in the center of the heat exchanger water inlet head at the middle of the unit Use this for maintenance etc In addition do not allow any of the unit s electrical parts such as the solenoid val...

Страница 9: ... cycle the refrigerator oil will dete riorate Never use existing refrigerant piping The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant...

Страница 10: ...ern flare machining dimension mm Example 1 Indoor No 1 15 A ø19 05 3 4 40 m 131 ft a ø6 35 1 4 10 m 32 ft No 2 72 B ø9 52 3 8 10 m 32 ft b ø9 52 3 8 5 m 16 ft No 3 15 c ø6 35 1 4 10 m 32 ft No 4 12 d ø6 35 1 4 10 m 32 ft No 5 24 e ø9 52 3 8 10 m 32 ft The total length of each liquid line is as follows ø19 05 3 4 A 40 m 131ft ø9 52 3 8 B b e 10 32 5 16 10 32 25 m 80 ft ø6 35 1 4 a c d 10 32 10 32 1...

Страница 11: ... amount as the refrigerat ing machine oil to coat flares and flange connections The refrigerating machine oil will degrade if it is mixed with a large amount of mineral oil Keep the ball valve closed until refrigerant charging to the pipes to be added on site has been completed Opening the valve before charging the refrigerant may result in unit damage Do not use a leak detection additive 9 3 Airt...

Страница 12: ...for heat source unit transmission Transmission line to be connected with indoor unit Terminal block TB3 for transmission line Other Terminal block TB7 for centralized control Erroneous connection does not allow the system to operate 8 In the case of connecting with an upper class controller or to conduct group operation in different refrigerant systems the control line for transmission is required...

Страница 13: ... S on the transmission cable block of the indoor unit IC c Connect terminals 1 M1 and 2 M2 on the transmission cable terminal block of the indoor unit IC that has the most recent address within the same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the heat source unit OC e On one heat sou...

Страница 14: ...ncy Display of remote controller Normal display Cooling heating flashes Normal display Normal display Defrost display No lighting Heat ready HO or PLEASE WAIT flashes Light out Cause This is not a trouble as it is just a selecting sound When multiple indoor units max 3 are connected to the same branch of the BC controller the heating cooling operation cannot be performed while another indoor unit ...

Страница 15: ...rent utilisez le réfrigérant R410A spécifié sur l appareil Lorsqu un réfrigérant différent est mélangé au réfrigérant d origine il se peut que le cycle du réfrigérant ne fonctionne pas correctement et que l appareil soit endommagé Si le climatiseur est installé dans une pièce relativement petite certaines mesures doivent être prises pour éviter que la concentration de réfrigé rant ne dépasse le se...

Страница 16: ...l appareil est raccordé au secteur sans fonctionner le chauffage du carter est toujours sous tension au niveau du compresseur 1 2 Précautions à prendre avec les dispo sitifs utilisant le réfrigérant R410A Précaution N utilisez pas les tuyaux de réfrigérant actuels Le vieux réfrigérant et l huile réfrigérante se trouvant dans les tuyaux con tiennent une large quantité de chlore qui pourrait abîmer ...

Страница 17: ...Ne les utilisez pas pour transporter l appareil car elles peuvent se révéler dangereuses Déchirez l emballage plastique et jetez le pour éviter que des enfants ne jouent avec car ils pourraient s étouffer Lors du transport de l unité source de chaleur veillez à la soutenir en quatre points Si vous ne la soutenez qu en 3 points elle risque d être instable et de tomber 4 Vérification des pièces livr...

Страница 18: ...ée et d évacuation de l eau En outre toujours installer un épurateur sur le tuyau d arrivée d eau Pour préserver la source de chaleur il est nécessaire d installer un épurateur à l arrivée de l eau devant circuler dans l appareil Le diagramme ci dessous donne un exemple d installation de la source de chaleur Installer une ventilation adéquate sur le tuyau d eau Après l envoi d eau dans le tuyau to...

Страница 19: ...de feu ou de flammes Si le gaz réfrigérant entrait en con tact avec une flamme quelle qu en soit la source par exemple une gazinière il se désagrégerait et générerait des gaz toxiques susceptibles de provo quer un empoisonnement au gaz Ne soudez jamais dans une pièce non aérée Vérifiez toujours qu il n y a pas de fuite de gaz après l installation des tuyaux de réfrigérant 8 1 Précaution Cet appare...

Страница 20: ...tuer correctement les interventions techniques par la suite toujours noter la taille et la longueur de chaque tuyau de réfrigérant ainsi que la quantité de charge supplémentaire ajoutée dans l espace prévu à cet effet sur l unité source de chaleur 9 1 Calcul de la charge supplémentaire de réfrigérant Calculer la quantité de la charge supplémentaire en se basant sur la longueur d extension et la ta...

Страница 21: ... de la soupape avant la charge du réfrigérant peut endommager l appareil Ne pas utiliser de liquide de détection de fuite 9 3 Test d étanchéité à l air évacuation et mise en place du réfrigérant 1 Test d étanchéité à l air Effectuez le test avec la vanne à bille de l unité source de chaleur fermée et pressurisez les tuyaux de connexion ainsi que l appareil intérieur à partir de l orifice de servic...

Страница 22: ...elopper les fils électriques d isolation thermique Fig 9 4 2 P 4 A Tuyau à basse pression B Tuyau à haute pression C Fil électrique D Bande de finition E Isolant Fig 9 4 3 P 4 Pénétrations Fig 9 4 4 P 4 A Mur interne caché B Mur externe C Mur externe exposé D Sol Etanchéification E Cheminée des tuyaux du toit F Partie pénétrant dans le coupe feu et le mur limite A Manchon B Isolant thermique C Cal...

Страница 23: ...on du système de contrôle centralisé à la borne de blindage S du bloc de terminaux TB7 de le contrôle centralisé En outre dans le cas d unités source de chaleur dont le connecteur d alimenta tion CN41 a été remplacé par un connecteur CN40 la borne de blindage S du bloc de terminaux TB7 du système de contrôle centralisé devrait égale ment être reliée à la terre Fixer fermement le câblage à la parti...

Страница 24: ...mum des câbles de transmission Câble M NET L1 et L3 L4 et L6 et L2 L6 200 m 656 ft 1 25 mm2 AWG16 ou plus Longueur du câble de la commande à distance c1 et c1 c2 c3 et c1 c2 c3 c4 200 m 656 ft 0 3 à 1 25 mm2 AWG22 à 16 3 Auxiliaire de transmission Longueur maximum des câbles de transmission Câble M NET 1 L8 L1 L2 L3 L5 L6 200 m 656 ft 1 25 mm2 AWG16 2 L8 L1 L2 L3 L5 L7 200 m 656 ft 1 25 mm2 AWG16 ...

Страница 25: ...teur fonctionne à vitesse extrêmement réduite pedant les 5 minutes après l activation du SW ou jusqu à ce que la température des tuyaux atteigne 35 C 95 F il fonctionne lentement pendant les 2 minutes qui suivent puis il fonctionne selon le préréglage Commande de réglage de la chaleur Le système est en train d être mis en marche Utilisez de nouveau la télécommande lorsque HO ou PLEASE WAIT a dis p...

Страница 26: ......

Страница 27: ......

Страница 28: ...HIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment Printed in Japan ...

Отзывы: