Water quality standard

Reference : Guideline of Water Quality for Refrigeration and Air Conditioning

Equipment. (JRA GL02E-1994)

3

Please consult with a water quality control specialist about water quality
control methods and water quality calculations before using anti-corrosive
solutions for water quality management.

4

When replacing a previously installed air conditioning device (even when
only the heat exchanger is being replaced), first conduct a water quality
analysis and check for possible corrosion.
Corrosion can occur in cold-water systems even if there has been no prior
signs of corrosion.
If the water quality level has dropped, please adjust water quality suffi-
ciently before replacing the unit.

7.4. Pump interlock

The heat source unit may become damaged if it is operated with no water circulat-
ing through the pipes.
Be sure to interlock unit operation and the water-circuit pump. Use the terminal
blocks for interlocking (TB8-3, 4) that can be found on the unit.
In the case of a pump interlock circuit signal connection to the TB8-3, 4, remove
the short-circuit wire. Also, to prevent mistaken error detection, resulting from a
poor connection, in the pressure valve 63PW, use a low maintained current of 5mA
or less.

[Fig. 7.4.1] (P.2)

A

Short-circuit wire (Connected before delivery from manufacturer)

B

Pump interlock circuit connection

pH (25

°

C) [77

°

F]

Electric conductivity (mS/m) (25

°

C) [77

°

F]

(

µ

 s/cm) (25

°

C) [77

°

F]

Chloride ion

(mg Cl

-

/

r

)

Sulfate ion

(mg SO4

2-

/

r

)

Acid consumption (pH4.8)

 

(mg CaCO

3

/

r

)

Total hardness

(mg CaCO

3

/

r

)

Calcium hardness (mg CaCO

3

/

r

)

Ionic silica

(mg SiO

2

/

r

)

Iron

(mg Fe/

r

)

Copper

(mg Cu/

r

)

Sulfide ion

(mg S

2-

/

r

)

Ammonium ion

(mg NH

4

+

/

r

)

Residual chlorine

(mg Cl/

r

)

Free carbon dioxide

(mg CO

2

/

r

)

Ryzner stability index

Standard

items

Refer-

ence

items

Items

Lower mid-range

temperature water system

7.0 ~ 8.0

30 or less

[300 or less]

50 or less

50 or less

50 or less

70 or less

50 or less

30 or less

1.0 or less

1.0 or less

not to be

detected

0.3 or less

0.25 or less

0.4 or less

7.0 ~ 8.0

30 or less

[300 or less]

50 or less

50 or less

50 or less

70 or less

50 or less

30 or less

0.3 or less

0.1 or less

not to be

detected

0.1 or less

0.3 or less

4.0 or less

Tendency

Recirculating

water

[20<T<60

°

C]

[68<T<140

°

F]

Make-up

water

Corrosive

Scale-

forming

8. Refrigerant piping installation

A

Residues in commercially available antioxidants may have adverse effects on
the equipment. Braze only with non-oxide brazing material. The use of other
brazing material may result in compressor damage.
(Refer to item 9.2. for detailed information on pipe connections and valve op-
erations.)

B

Never perform heat source unit piping connection work when it is rain-
ing.

 Warning

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

Use a vacuum pump with a reverse flow check valve.

- If the vacuum pump does not have a reverse flow check valve, the vacuum

pump oil may flow back into the refrigerant cycle and cause deterioration of
the refrigerator oil and other trouble.

Do not use the tools shown below used with conventional refrigerant.
(Gauge manifold, charge hose, gas leak detector, check valve, refrigerant
charge base, vacuum gauge, refrigerant recovery equipment)

- Mixing of conventional refrigerant and refrigerator oil may cause the refrig-

erator oil to deteriorate.

- Mixing of water will cause the refrigerator oil to deteriorate.
- R410A refrigerant does not contain any chlorine. Therefore, gas leak detec-

tors for conventional refrigerants will not react to it.

Manage the tools more carefully than normal.

- If dust, dirt, or water gets in the refrigerant cycle, the refrigerator oil will dete-

riorate.

Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil

in the existing piping will cause the new refrigerant to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

the compressor may fail.

Do not use a charging cylinder.

- Using a charging cylinder may cause the refrigerant to deteriorate.

Do not use special detergents for washing piping.

8.2. Refrigerant piping system

Connection Example

[Fig. 8.2.1]

 

(P.3)

Å

Heat source model

ı

 High press. side

Ç

Low press. side

Î

Total capacity of indoor units

Liquid line

Ï

Gas line

Ì

High press. gas pipe

Ó

Low press. gas pipe

¬

Liquid pipe

Ô

Model number

A

BC controller (standard)

B

BC controller (main)

C

BC controller (sub)

D

Indoor unit (06 ~ 54)

E

Indoor unit (72, 96)

City Multi WR2 Series is constituted by an end branching system in which the
refrigerant piping from heat source unit is branched at BC controller and connected
to each indoor unit.
The connection method adapted is brazing connection for high pressure pipe and
low pressure pipe between heat source unit and BC controller, and flare connec-
tion between BC controller and indoor unit. Brazing connection is employed for
joint pipe set and branch pipe set.

 Warning:

Always use extreme care to prevent the refrigerant gas from leaking while
using fire or flame. If the refrigerant gas comes in contact with a flame from
any source, such as a gas stove, it breaks down and generates a poisonous
gas which can cause gas poisoning. Never weld in an unventilated room.
Always conduct an inspection for gas leakage after installation of the refrig-
erant piping has been completed.

8.1. Caution

This unit uses refrigerant R410A. Follow the local regulations on materials and
pipe thickness when selecting pipes.

1

Use the following materials for refrigeration piping.

Material: Use refrigerant piping made of phosphorus deoxidized copper.
In addition, be sure that the inner and outer surfaces of the pipes are clean
and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils,
moisture, or any other contaminant.

2

Commercially available piping often contains dust and other materials.  Always
blow it clean with a dry inert gas.

3

Use care to prevent dust, water or other contaminants from entering the piping
during installation.

4

Reduce the number of bending portions as much as possible, and make bend-
ing radius as big as possible.

5

Always observe the restrictions on the refrigerant piping (such as rated length,
the difference between high/low pressures, and piping diameter).  Failure to do
so can result in equipment failure or a decline in heating/cooling performance.

6

Either a lack or an excess of refrigerant causes the unit to make an emergency
stop. Charge the system with an appropriate amount of refrigerant. At such a
time, always properly charge the unit.  When servicing, always check the notes
concerning pipe length and amount of additional refrigerant at both locations,
the refrigerant volume calculation table on the back of the service panel and
the additional refrigerant section on the labels for the combined number of
indoor units.

7

Use liquid refrigerant to fill the system.

8

Never use refrigerant to perform an air purge.  Always evacuate using a vacuum
pump.

9

Always insulate the piping properly.  Insufficient insulation will result in a de-
cline in heating/cooling performance, water drops from condensation and other
such problems.

0

When connecting the refrigerant piping, make sure the ball valve of the heat
source unit is completely closed (the factory setting) and do not operate it until
the refrigerant piping for the heat source and indoor units has been connected,
a refrigerant leakage test has been performed and the evacuation process has
been completed.

Содержание City Multi PQRY-P72TGMU-A

Страница 1: ...r safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte For use with R410A ...

Страница 2: ...4 ø14 9 16 Anchoring hole C Top view A Piping space for side piping B Heat source unit C Service space front side D Top view D Anti vibration pad etc E Concrete base E Piping space for top piping F Piping space for side piping G Heat source unit H Front view A Water circulation pipe B Close valve C Close valve D Water outlet A Short circuit wire Connected before delivery from manufacturer B Pump i...

Страница 3: ...ow press gas pipe ø19 05 3 4 ø22 2 7 8 ø28 58 1 1 8 B Unit mm in Î Total capacity of indoor units 54 55 72 Liquid line ø9 52 3 8 ø9 52 3 8 Ï Gas line ø15 88 5 8 ø19 05 3 4 A Unit mm in Å Heat source model P72 P96 ı High press side ø15 88 5 8 ø19 05 3 4 Ç Low press side ø19 05 3 4 ø22 2 7 8 Fig 9 2 2 9 2 9 Fig 9 2 1 A B 1 3 A Ball valve Low press side flanged type B Ball valve High press side flare...

Страница 4: ...rial C Lagging D Caulking material E Band F Waterproofing laye G Sleeve with edge H Lagging material I Mortar or other incombustible caulking J Incombustible heat insulation material A Power source B Transmission line C Ground screw D C C B B E F G H I J A LO HI LO HI B A K J L H M C D E N O F G I Fig 9 3 1 Fig 9 3 3 Fig 9 3 2 9 3 A A Nitrogen gas B To indoor unit C System analyzer D Lo knob E Hi ...

Страница 5: ... BC M1M2S 52 BS M1M2S 55 BC M1M2S 54 M1M2S System controller L3 L 6 L4 L 5 r 2 r 4 r 1 A B A B A B A B CN40 CN40 A B C E D M1M2 M1M2S TB7 TB3 IC 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 MA MA MA OC M1M2 M1M2S TB7 TB3 CN40 53 OC c 1 c4 c 3 BC M1M2S 52 BS M...

Страница 6: ...installing the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heater stove oven or other heat source it may generate noxious gases Do not reconstruct or ch...

Страница 7: ...nt If the conventional refrigerant and refrigerator oil are mixed in the R410A the refrigerant may deteriorated If water is mixed in the R410A the refrigerator oil may deteriorate Since R410A does not contain any chlorine gas leak detectors for conven tional refrigerants will not react to it Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate Be especi...

Страница 8: ...excess air Compressed water may form in the low temperature sections of heat source unit Use a drainage pipe connected to the drain valve at the base of the unit to drain the water There is a water vent plug in the center of the heat exchanger water inlet head at the middle of the unit Use this for maintenance etc In addition do not allow any of the unit s electrical parts such as the solenoid val...

Страница 9: ... cycle the refrigerator oil will dete riorate Never use existing refrigerant piping The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant...

Страница 10: ...ern flare machining dimension mm Example 1 Indoor No 1 15 A ø19 05 3 4 40 m 131 ft a ø6 35 1 4 10 m 32 ft No 2 72 B ø9 52 3 8 10 m 32 ft b ø9 52 3 8 5 m 16 ft No 3 15 c ø6 35 1 4 10 m 32 ft No 4 12 d ø6 35 1 4 10 m 32 ft No 5 24 e ø9 52 3 8 10 m 32 ft The total length of each liquid line is as follows ø19 05 3 4 A 40 m 131ft ø9 52 3 8 B b e 10 32 5 16 10 32 25 m 80 ft ø6 35 1 4 a c d 10 32 10 32 1...

Страница 11: ... amount as the refrigerat ing machine oil to coat flares and flange connections The refrigerating machine oil will degrade if it is mixed with a large amount of mineral oil Keep the ball valve closed until refrigerant charging to the pipes to be added on site has been completed Opening the valve before charging the refrigerant may result in unit damage Do not use a leak detection additive 9 3 Airt...

Страница 12: ...for heat source unit transmission Transmission line to be connected with indoor unit Terminal block TB3 for transmission line Other Terminal block TB7 for centralized control Erroneous connection does not allow the system to operate 8 In the case of connecting with an upper class controller or to conduct group operation in different refrigerant systems the control line for transmission is required...

Страница 13: ... S on the transmission cable block of the indoor unit IC c Connect terminals 1 M1 and 2 M2 on the transmission cable terminal block of the indoor unit IC that has the most recent address within the same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the heat source unit OC e On one heat sou...

Страница 14: ...ncy Display of remote controller Normal display Cooling heating flashes Normal display Normal display Defrost display No lighting Heat ready HO or PLEASE WAIT flashes Light out Cause This is not a trouble as it is just a selecting sound When multiple indoor units max 3 are connected to the same branch of the BC controller the heating cooling operation cannot be performed while another indoor unit ...

Страница 15: ...rent utilisez le réfrigérant R410A spécifié sur l appareil Lorsqu un réfrigérant différent est mélangé au réfrigérant d origine il se peut que le cycle du réfrigérant ne fonctionne pas correctement et que l appareil soit endommagé Si le climatiseur est installé dans une pièce relativement petite certaines mesures doivent être prises pour éviter que la concentration de réfrigé rant ne dépasse le se...

Страница 16: ...l appareil est raccordé au secteur sans fonctionner le chauffage du carter est toujours sous tension au niveau du compresseur 1 2 Précautions à prendre avec les dispo sitifs utilisant le réfrigérant R410A Précaution N utilisez pas les tuyaux de réfrigérant actuels Le vieux réfrigérant et l huile réfrigérante se trouvant dans les tuyaux con tiennent une large quantité de chlore qui pourrait abîmer ...

Страница 17: ...Ne les utilisez pas pour transporter l appareil car elles peuvent se révéler dangereuses Déchirez l emballage plastique et jetez le pour éviter que des enfants ne jouent avec car ils pourraient s étouffer Lors du transport de l unité source de chaleur veillez à la soutenir en quatre points Si vous ne la soutenez qu en 3 points elle risque d être instable et de tomber 4 Vérification des pièces livr...

Страница 18: ...ée et d évacuation de l eau En outre toujours installer un épurateur sur le tuyau d arrivée d eau Pour préserver la source de chaleur il est nécessaire d installer un épurateur à l arrivée de l eau devant circuler dans l appareil Le diagramme ci dessous donne un exemple d installation de la source de chaleur Installer une ventilation adéquate sur le tuyau d eau Après l envoi d eau dans le tuyau to...

Страница 19: ...de feu ou de flammes Si le gaz réfrigérant entrait en con tact avec une flamme quelle qu en soit la source par exemple une gazinière il se désagrégerait et générerait des gaz toxiques susceptibles de provo quer un empoisonnement au gaz Ne soudez jamais dans une pièce non aérée Vérifiez toujours qu il n y a pas de fuite de gaz après l installation des tuyaux de réfrigérant 8 1 Précaution Cet appare...

Страница 20: ...tuer correctement les interventions techniques par la suite toujours noter la taille et la longueur de chaque tuyau de réfrigérant ainsi que la quantité de charge supplémentaire ajoutée dans l espace prévu à cet effet sur l unité source de chaleur 9 1 Calcul de la charge supplémentaire de réfrigérant Calculer la quantité de la charge supplémentaire en se basant sur la longueur d extension et la ta...

Страница 21: ... de la soupape avant la charge du réfrigérant peut endommager l appareil Ne pas utiliser de liquide de détection de fuite 9 3 Test d étanchéité à l air évacuation et mise en place du réfrigérant 1 Test d étanchéité à l air Effectuez le test avec la vanne à bille de l unité source de chaleur fermée et pressurisez les tuyaux de connexion ainsi que l appareil intérieur à partir de l orifice de servic...

Страница 22: ...elopper les fils électriques d isolation thermique Fig 9 4 2 P 4 A Tuyau à basse pression B Tuyau à haute pression C Fil électrique D Bande de finition E Isolant Fig 9 4 3 P 4 Pénétrations Fig 9 4 4 P 4 A Mur interne caché B Mur externe C Mur externe exposé D Sol Etanchéification E Cheminée des tuyaux du toit F Partie pénétrant dans le coupe feu et le mur limite A Manchon B Isolant thermique C Cal...

Страница 23: ...on du système de contrôle centralisé à la borne de blindage S du bloc de terminaux TB7 de le contrôle centralisé En outre dans le cas d unités source de chaleur dont le connecteur d alimenta tion CN41 a été remplacé par un connecteur CN40 la borne de blindage S du bloc de terminaux TB7 du système de contrôle centralisé devrait égale ment être reliée à la terre Fixer fermement le câblage à la parti...

Страница 24: ...mum des câbles de transmission Câble M NET L1 et L3 L4 et L6 et L2 L6 200 m 656 ft 1 25 mm2 AWG16 ou plus Longueur du câble de la commande à distance c1 et c1 c2 c3 et c1 c2 c3 c4 200 m 656 ft 0 3 à 1 25 mm2 AWG22 à 16 3 Auxiliaire de transmission Longueur maximum des câbles de transmission Câble M NET 1 L8 L1 L2 L3 L5 L6 200 m 656 ft 1 25 mm2 AWG16 2 L8 L1 L2 L3 L5 L7 200 m 656 ft 1 25 mm2 AWG16 ...

Страница 25: ...teur fonctionne à vitesse extrêmement réduite pedant les 5 minutes après l activation du SW ou jusqu à ce que la température des tuyaux atteigne 35 C 95 F il fonctionne lentement pendant les 2 minutes qui suivent puis il fonctionne selon le préréglage Commande de réglage de la chaleur Le système est en train d être mis en marche Utilisez de nouveau la télécommande lorsque HO ou PLEASE WAIT a dis p...

Страница 26: ......

Страница 27: ......

Страница 28: ...HIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment Printed in Japan ...

Отзывы: