–94–
No cooling
No heating
Check disconnection or looseness
of connectors.
Is there a problem?
Operate in cooling or heating (1 system
only when there are plural systems)
Cooling or heating
operation?
Heating operation
Note 1
Check if LEV 1 are fully open
LEV 1 fully open?
LEV3 are not
controlled
Check if LEV 1 are fully shut.
Yes
Note 2
No
Yes
No
Yes
No
Yes
No
Yes
Check if LEV3 is controlled by
superheat.
LEV3 is not controlled.
Check if SVM1 is ON.
SVM1 ON
Check if SVA, SVC are ON.
SVA, SVC ON
Check if SVB is OFF.
SVB OFF
Check if LEV 3 are controlled by
differential pressure.
Completion
Check SVB
Check SVA, SVC
Check SVM1
Check LEV3
Correct the problem.
Check LEV1
SVB ON
Check if SVB is ON.
SVA, SVC OFF
Check if SVA, SVC are OFF.
SVM1 OFF
Check if SVM1 is OFF.
LEV 1 fully shut?
Yes
No
Note 2
No
No
No
Yes
Yes
Yes
Note 3
Note 3
No
Yes
Yes
No
3) LEV, Solenoid Valve Troubleshooting Flow
Содержание CITY MULTI P500YMF-C
Страница 2: ......
Страница 15: ... 13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board ...
Страница 16: ... 14 Y C board SNB board ...
Страница 17: ... 15 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5 ...
Страница 18: ... 16 RELAY 10 board RELAY 4 board ...
Страница 22: ... 20 3 Electrical Wiring Diagram PURY P400 500YMF C ...
Страница 73: ... 71 Check Valves Block2 1 3 5 7 6 4 2 CV5b CV4b CV6b CV2b ST1 BV1 BV2 CV3b Check Valves Block2 1 3 7 2 4 5 6 ...
Страница 91: ... 89 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...