–83–
(3)
Investigation of transmission wave shape/noise
Control is performed by exchanging signals between outdoor unit, indoor unit and remote controller by M-NET
transmission. If noise should enter into the transmission line, the normal transmission will be hindered causing
erroneous operation.
1) Symptom caused by the noise entered into transmission line
Cause
Erroneous operation
Error code
Signal changes and is misjudged as the signal of other
address.
Transmission wave shape changes to other signal due to
noise.
Transmission wave shape changes due to noise, and can
not be received normally thus providing no reply (ACK).
Transmission can not be made continuously due to the
entry of fine noise.
Transmission can be made normally, but reply (ACK) or
answer can not be issued normally due to noise.
2)
Method to confirm wave shape
Check the wave shape of transmission line with an oscilloscope to confirm that the following conditions are being
satisfied.
1
The figure should be 104
µ
s/bit
±
1%.
2
No finer wave shape (noise) than the transmission signal (52
µ
s
±
1%) should be allowed. *1
3
The sectional voltage level of transmission signal should be as follows.
*1 However, minute noise from the DC-DC converter or inverter operation may be picked up.
Noise entered into
transmission line
6600
6602
6607
6603
6607
6608
<with transmission>
<without transmission>
No fine noise allowed *1
No fine noise allowed
*1
Logic value
Transmission line voltage level
0
V
HL
= 2.0V or more
1
V
BN
= 1.3V or less
V
HL
V
BN
52
µ
s
Logical
52
µ
s
52
µ
s
Logical
52
µ
s
value “0”
52
µ
s
value “1”
Содержание CITY MULTI P500YMF-C
Страница 2: ......
Страница 15: ... 13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board ...
Страница 16: ... 14 Y C board SNB board ...
Страница 17: ... 15 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5 ...
Страница 18: ... 16 RELAY 10 board RELAY 4 board ...
Страница 22: ... 20 3 Electrical Wiring Diagram PURY P400 500YMF C ...
Страница 73: ... 71 Check Valves Block2 1 3 5 7 6 4 2 CV5b CV4b CV6b CV2b ST1 BV1 BV2 CV3b Check Valves Block2 1 3 7 2 4 5 6 ...
Страница 91: ... 89 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...