–63–
(2)
Refrigerant adjustment in Cooling season (Flow chart)
In case of PURY-P400, 500YMF-C
YES
NO
Adjustment starts.
Start cooling operation of all indoor
units in a test run mode. Note 1
Has the
compressor been
operated for more than
30min?
Was the operation
condition stabilized?
The high pressure
> 13kg/cm2G?
TH1
≤
115˚C?
Are all indoor
units SHs more
than 6deg?
Is the LEV opening
degree stable when SH
< 6deg?
Is the
thermostat turned
on/off in order for the indoor
unit to prevent from
frosting?
Adjustment completed.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Fill refrigerant little by little from the
low-pressure side service port.
Stop the refrigerant volume adjustment
and retrieve the refrigerant. After
evacuating air, fill the specified volume
of refrigerant.
Retrieve the refrigerant little by little
from the low-pressure side service
port.
Note 1) As the refrigerant volume can not be adjusted in the heating mode,
retrieve the refrigerant, evacuate air and then fill the specified
volume of refrigerant if it is necessary to adjust the refrigerant
volume in the winter season.
5deg
≤
SC11?
10
≤
SC16
≤
30deg?
30deg < SC16?
TH1
≤
110˚C?
Fill refrigerant little by little from the
low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Fill refrigerant little by little from the
low-pressure side service port.
Fill refrigerant little by little from the
low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Note 2
Note 3
Note 2) SC11 : Liquid refrigerant sub-cool for BC controller inlet
Note 3) SC16 : Liquid refrigerant sub-cool for BC controller outlet
Содержание CITY MULTI P500YMF-C
Страница 2: ......
Страница 15: ... 13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board ...
Страница 16: ... 14 Y C board SNB board ...
Страница 17: ... 15 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5 ...
Страница 18: ... 16 RELAY 10 board RELAY 4 board ...
Страница 22: ... 20 3 Electrical Wiring Diagram PURY P400 500YMF C ...
Страница 73: ... 71 Check Valves Block2 1 3 5 7 6 4 2 CV5b CV4b CV6b CV2b ST1 BV1 BV2 CV3b Check Valves Block2 1 3 7 2 4 5 6 ...
Страница 91: ... 89 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...