Setup and Procedures before Operation
Start-up Procedure
6 – 6
6.4 Start-up
Procedure
6.4.1 CANopen
쏐
405 mode
6.4.2
11 bit/29 bit CAN-ID Layer 2 Mode
Step
Action
Reference
(Section)
1
Set the function mode (Un\G21)
2
Store the buffer memory configuration (set Un\G22 then turn Y(n+1)F ON)
3
Restart the ME3CAN1-L (turn Yn2 ON)
4
Set the baud rate (Un\G24)
5
Set the Node Address (Un\G27)
6
Store the buffer memory configuration (set Un\G22 then turn Y(n+1)F ON)
7
Restart the ME3CAN1-L (turn Yn2 ON)
8
CANopen
쏐
NMT Master:
Configure OD Index 1F80
H
and if necessary the OD Index 1F90
H
—
Store the OD configuration (OD Index 1010
H
)
—
Restart the ME3CAN1-L (turn Yn2 ON)
9
Setup Heartbeat producing/consuming
10
Setup RPDO communication and mapping parameter
11
Setup TPDO communication and mapping parameter
12
On the NMT Master:
Setup NMT Slave assignment (OD Index 1F81
H
)
Setup NMT Slave Identification data (OD Indexes 1F84
H
to 1F88
H
),
the OD Index 1F84
H
is in most cases sufficient.
Setup the Boot time (OD Index 1F89
H
)
13
Store the OD configuration (OD Index 1010
H
)
Tab. 6-4:
Start-up procedure for CANopen
쏐
405 mode
Step
Action
Reference
(Section)
1
Set the function mode (Un\G21)
2
Store the buffer memory configuration (set Un\G22 then turn Y(n+1)F ON)
3
Restart the ME3CAN1-L (turn Yn2 ON)
4
Set the baud rate (Un\G24)
5
Store the buffer memory configuration (set Un\G22 then turn Y(n+1)F ON)
6
Restart the ME3CAN1-L (turn Yn2 ON)
7
Setup Pre-defined Layer 2 message configuration
8
Setup buffer memory location of the Receive / Transmit Process Data
9
Setup PLC RUN>STOP messages
10
Store the buffer memory configuration (set Un\G22 then turn Y(n+1)F ON)
Tab. 6-5:
Start-up procedure for 11 bit/29 bit CAN-ID Layer 2 Mode
Содержание CANopen ME3CAN1-L
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...IV ...
Страница 18: ...Abbreviations and Generic Terms Overview MELSEC L Series CANopen Module ME3CAN1 L 1 4 ...
Страница 22: ...System Configuration System Equipment 2 4 MITSUBISHI ELECTRIC ...
Страница 66: ...Detailed Description of the Module Buffer Memory Details Layer 2 Message Mode 3 44 MITSUBISHI ELECTRIC ...
Страница 144: ...Programming CANopen PDO Communication using Function Blocks 7 6 MITSUBISHI ELECTRIC Fig 7 6 Example Program 2 ...
Страница 146: ...Programming CANopen PDO Communication using Function Blocks 7 8 MITSUBISHI ELECTRIC Fig 7 8 Example Program 4 ...
Страница 148: ...Programming CANopen PDO Communication using Function Blocks 7 10 MITSUBISHI ELECTRIC Fig 7 10 Example Program 6 ...
Страница 150: ...Programming CANopen PDO Communication using Function Blocks 7 12 MITSUBISHI ELECTRIC Fig 7 12 Example Program 8 ...
Страница 152: ...Programming CANopen PDO Communication using Function Blocks 7 14 MITSUBISHI ELECTRIC Fig 7 14 Example Program 10 ...
Страница 154: ...Programming CANopen PDO Communication using Function Blocks 7 16 MITSUBISHI ELECTRIC Fig 7 16 Example Program 12 ...
Страница 156: ...Programming CANopen PDO Communication using Function Blocks 7 18 MITSUBISHI ELECTRIC Fig 7 18 Example Program 14 ...
Страница 158: ...Programming CANopen PDO Communication using Function Blocks 7 20 MITSUBISHI ELECTRIC Fig 7 20 Example Program 16 ...
Страница 160: ...Programming Layer 2 Communication 7 22 MITSUBISHI ELECTRIC Local Label Setting Fig 7 22 Local Label for this example 1 ...
Страница 161: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 23 Fig 7 23 Local Label for this example 2 ...
Страница 162: ...Programming Layer 2 Communication 7 24 MITSUBISHI ELECTRIC Program Fig 7 24 Example Program 1 ...
Страница 163: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 25 Fig 7 25 Example Program 2 ...
Страница 164: ...Programming Layer 2 Communication 7 26 MITSUBISHI ELECTRIC Fig 7 26 Example Program 3 ...
Страница 165: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 27 Fig 7 27 Example Program 4 ...
Страница 166: ...Programming Layer 2 Communication 7 28 MITSUBISHI ELECTRIC Fig 7 28 Example Program 5 ...
Страница 167: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 29 Fig 7 29 Example Program 6 ...
Страница 172: ...Programming Layer 2 Communication 7 34 MITSUBISHI ELECTRIC Fig 7 39 Example Program 2 Set message parameter to module ...
Страница 178: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 40 ...
Страница 184: ...Troubleshooting Error Code and Error Message Summary 8 6 MITSUBISHI ELECTRIC ...
Страница 187: ......