Wiring
Setup and Procedures before Operation
MELSEC-L Series – CANopen
Module ME3CAN1-L
6 – 3
6.3 Wiring
6.3.1 Wiring
Precautions
Please observe the following precautions for external wiring:
●
Perform class D grounding (grounding resistance: 100 or less) to the shield of the twisted shield
cable (refer to section 6.3.2). Do not use common grounding with heavy electrical systems.
●
Always confirm the connector layout before connecting the CAN bus to the ME3CAN1-L.
(For the signal layout of the connector please refer to section 3.1.2)
●
Make sure to properly wire to the CAN bus connector in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunc-
tions, or damage to the product.
–
The size of the cable end should follow the dimensions described in the manual.
–
Tightening torque should follow the specifications in the manual.
–
Twist the end of strand wire and make sure that there are no loose wires.
–
Do not solder-plate the electric wire ends.
–
Do not connect more than the specified number of wires or electric wires of unspecified size.
–
Affix the electric wires so that neither the connector nor the connected parts are directly
stressed.
●
Make sure that foreign matter such as cutting chips and wire scraps does not enter the ME3CAN1-L.
Failure to observe this could lead to fires, faults or malfunctioning.
●
Make sure to affix the CAN bus connector with fixing screws.
Tightening torque should be within 0.20 to 0.28 Nm. Loose connections may cause malfunctions.
●
Do not disconnect the CAN bus cable connected to the ME3CAN1-L by pulling the cable section.
Be sure to hold the connector connected to the ME3CAN1-L. Pulling the cable while it is connected
to the ME3CAN1-L may lead to malfunctioning or damage of the ME3CAN1-L or cable.
●
Make sure to observe the following precautions in order to prevent any damage to the machinery
or accidents due to abnormal data written to the PLC under the influence of noise:
–
Do not bundle or adjacently lay the communication cable connected to the ME3CAN1-L with
the main circuit line, power line, or the load line other than that for the PLC. Separate these by
100 mm as a guide. Failure to observe this could lead to malfunctioning caused by noise, surge,
or induction.
–
Ground the shield wire or shield of a shielded cable. Do not use common grounding with heavy
electrical systems.
●
Place the communication cable in grounded metallic ducts or conduits both inside and outside of
the control panel whenever possible.
Содержание CANopen ME3CAN1-L
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...IV ...
Страница 18: ...Abbreviations and Generic Terms Overview MELSEC L Series CANopen Module ME3CAN1 L 1 4 ...
Страница 22: ...System Configuration System Equipment 2 4 MITSUBISHI ELECTRIC ...
Страница 66: ...Detailed Description of the Module Buffer Memory Details Layer 2 Message Mode 3 44 MITSUBISHI ELECTRIC ...
Страница 144: ...Programming CANopen PDO Communication using Function Blocks 7 6 MITSUBISHI ELECTRIC Fig 7 6 Example Program 2 ...
Страница 146: ...Programming CANopen PDO Communication using Function Blocks 7 8 MITSUBISHI ELECTRIC Fig 7 8 Example Program 4 ...
Страница 148: ...Programming CANopen PDO Communication using Function Blocks 7 10 MITSUBISHI ELECTRIC Fig 7 10 Example Program 6 ...
Страница 150: ...Programming CANopen PDO Communication using Function Blocks 7 12 MITSUBISHI ELECTRIC Fig 7 12 Example Program 8 ...
Страница 152: ...Programming CANopen PDO Communication using Function Blocks 7 14 MITSUBISHI ELECTRIC Fig 7 14 Example Program 10 ...
Страница 154: ...Programming CANopen PDO Communication using Function Blocks 7 16 MITSUBISHI ELECTRIC Fig 7 16 Example Program 12 ...
Страница 156: ...Programming CANopen PDO Communication using Function Blocks 7 18 MITSUBISHI ELECTRIC Fig 7 18 Example Program 14 ...
Страница 158: ...Programming CANopen PDO Communication using Function Blocks 7 20 MITSUBISHI ELECTRIC Fig 7 20 Example Program 16 ...
Страница 160: ...Programming Layer 2 Communication 7 22 MITSUBISHI ELECTRIC Local Label Setting Fig 7 22 Local Label for this example 1 ...
Страница 161: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 23 Fig 7 23 Local Label for this example 2 ...
Страница 162: ...Programming Layer 2 Communication 7 24 MITSUBISHI ELECTRIC Program Fig 7 24 Example Program 1 ...
Страница 163: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 25 Fig 7 25 Example Program 2 ...
Страница 164: ...Programming Layer 2 Communication 7 26 MITSUBISHI ELECTRIC Fig 7 26 Example Program 3 ...
Страница 165: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 27 Fig 7 27 Example Program 4 ...
Страница 166: ...Programming Layer 2 Communication 7 28 MITSUBISHI ELECTRIC Fig 7 28 Example Program 5 ...
Страница 167: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 29 Fig 7 29 Example Program 6 ...
Страница 172: ...Programming Layer 2 Communication 7 34 MITSUBISHI ELECTRIC Fig 7 39 Example Program 2 Set message parameter to module ...
Страница 178: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 40 ...
Страница 184: ...Troubleshooting Error Code and Error Message Summary 8 6 MITSUBISHI ELECTRIC ...
Страница 187: ......