Network Management
Functions
MELSEC-L Series – CANopen
Module ME3CAN1-L
4 – 41
Object 1F80
H
: NMT start-up
By using a SDO access, this object configures the start-up behavior of a CANopen
device. This object
configures the start-up behaviour of a CANopen® device via SDO access. If the node is set as Master
without the flying master capability, the node starts as NMT master and ignores all NMT commands
from the network.
After the ME3CAN1-L has been configured as the NMT master, the parameter values have to be stored
(refer to section 4.6.10) and the module has to be restarted by Yn2 or by NMT request Reset Node
(refer to sections 3.3.2 and 4.8.8.).
Fig. 4-30:
Bit allocation for object 1F80
H
: NMT start-up
Bit/Item
Description
Remark
NMT master
Setting of module:
Bit = 0: NMT slave
Bit = 1: NMT master
앫
If this bit is set to 0, all settings of object 1F80
H
and 1F81
H
are ignored.
앫
Only one (active) NMT master is allowed in a
CANopen
network.
Start all nodes
How to start the NMT slaves by sending NMT
service:
Bit = 0: Send NMT service
Start remote node
for each
NMT slave.
Bit = 1: Send NMT service
Start all remote nodes
.
If this bit is set to 1:
앫
Consider fig. 4-29 (NMT Master simple startup)
앫
Don't use this setting to start remote nodes
which are not assigned to the master via index
1F81
H
NMT master
start
How to shift to NMT state
Operational
:
Bit = 0: Shift automatically
Bit = 1: Do not shift automatically
If this bit is set to 1:
앫
The NMT Master has to be shifted manually into
NMT state
Operational
. This can be done by using
the SDO write command for object 1F82
H
. The
start-up process will be suspended as long the
device is not in NMT State
Operational
. Refer to
section 4.8.8 and section 3.5.18.
Start node
How to start the NMT slaves:
Bit = 0: The NMT master shall start the NMT slaves.
Bit = 1: Not the NMT master but the PLC application
shall start the NMT slaves.
If this bit is set to 1:
앫
Consider the result behavior shown in fig. 4-29
and fig. 4-31.
Reset all nodes
Describes which NMT service shall be executed if an
error control event occurs in an assigned manda-
tory NMT slave (refer to section 4.8.6).
Bit = 0: NMT service
Reset communication
for the
erroneous CANopen
device.
Bit = 1: NMT service
Reset communication all nodes
앫
For optional NMT Slaves, NMT service reset com-
munication for this device must be executed.
앫
If bit 6 (stop all nodes) is set to 1, this bit setting
will be ignored by the mandatory NMT slaves.
Flying master
Bit = 0: Do not use flying master service.
Bit = 1: Use flying master service.
앫
If the device is lost at the flying master negotia-
tion, the device works as NMT slave.
앫
When using flying master service, all NMT mas-
ters in the network need to be set as flying
master.
앫
When using flying master service, additional set-
tings need to be considered (refer to section
4.8.10).
Stop all nodes
How to stop nodes if an error control event occurs
in an assigned mandatory NMT slave:
Bit = 0: Do not stop all nodes.
Bit = 1: Stop all nodes
앫
If this setting is set to 1, the bit 4 setting is
ignored.
앫
To restart the network, the NMT master has to be
reset manually by Yn2 or by executing the SDO
write command for the object 1F82
H
to execute
the NMT service
Reset communication
or
Reset
node for all nodes
. (Refer to sections 3.3.2, 4.8.8
Tab. 4-29:
Description of object 1F80
H
: NMT start-up
Bit 5
Bit 4
Bit 0
0
H
Stop all
nodes
Bit 31 ... Bit 7
Bit 1
Bit 2
Bit 3
Bit 6
Flying
master
Reset all
nodes
Start node
NMT master
start
Start all
nodes
NMT
master
Содержание CANopen ME3CAN1-L
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...IV ...
Страница 18: ...Abbreviations and Generic Terms Overview MELSEC L Series CANopen Module ME3CAN1 L 1 4 ...
Страница 22: ...System Configuration System Equipment 2 4 MITSUBISHI ELECTRIC ...
Страница 66: ...Detailed Description of the Module Buffer Memory Details Layer 2 Message Mode 3 44 MITSUBISHI ELECTRIC ...
Страница 144: ...Programming CANopen PDO Communication using Function Blocks 7 6 MITSUBISHI ELECTRIC Fig 7 6 Example Program 2 ...
Страница 146: ...Programming CANopen PDO Communication using Function Blocks 7 8 MITSUBISHI ELECTRIC Fig 7 8 Example Program 4 ...
Страница 148: ...Programming CANopen PDO Communication using Function Blocks 7 10 MITSUBISHI ELECTRIC Fig 7 10 Example Program 6 ...
Страница 150: ...Programming CANopen PDO Communication using Function Blocks 7 12 MITSUBISHI ELECTRIC Fig 7 12 Example Program 8 ...
Страница 152: ...Programming CANopen PDO Communication using Function Blocks 7 14 MITSUBISHI ELECTRIC Fig 7 14 Example Program 10 ...
Страница 154: ...Programming CANopen PDO Communication using Function Blocks 7 16 MITSUBISHI ELECTRIC Fig 7 16 Example Program 12 ...
Страница 156: ...Programming CANopen PDO Communication using Function Blocks 7 18 MITSUBISHI ELECTRIC Fig 7 18 Example Program 14 ...
Страница 158: ...Programming CANopen PDO Communication using Function Blocks 7 20 MITSUBISHI ELECTRIC Fig 7 20 Example Program 16 ...
Страница 160: ...Programming Layer 2 Communication 7 22 MITSUBISHI ELECTRIC Local Label Setting Fig 7 22 Local Label for this example 1 ...
Страница 161: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 23 Fig 7 23 Local Label for this example 2 ...
Страница 162: ...Programming Layer 2 Communication 7 24 MITSUBISHI ELECTRIC Program Fig 7 24 Example Program 1 ...
Страница 163: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 25 Fig 7 25 Example Program 2 ...
Страница 164: ...Programming Layer 2 Communication 7 26 MITSUBISHI ELECTRIC Fig 7 26 Example Program 3 ...
Страница 165: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 27 Fig 7 27 Example Program 4 ...
Страница 166: ...Programming Layer 2 Communication 7 28 MITSUBISHI ELECTRIC Fig 7 28 Example Program 5 ...
Страница 167: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 29 Fig 7 29 Example Program 6 ...
Страница 172: ...Programming Layer 2 Communication 7 34 MITSUBISHI ELECTRIC Fig 7 39 Example Program 2 Set message parameter to module ...
Страница 178: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 40 ...
Страница 184: ...Troubleshooting Error Code and Error Message Summary 8 6 MITSUBISHI ELECTRIC ...
Страница 187: ......