VII
Control ]
- 85 -
HWE10060
GB
Control at Initial Start-up
-10- Peak-demand control
General idea about demand control in the system with a combination of a heat pump and a combustion-type hot water boiler.
→During peak-demand hours, the operation of the air conditioning units is given higher priority than that of the heat pump units.
1.Individual system
The peak-demand control function is a function that restricts the maximum capacity of the units. The maximum operation
capacities of the units are restricted to specific levels relative to the maximum capacity of the units (= the compressors are
operating at the maximum rotation speed (100 Hz on the unit described in this manual)) being set as 100%.
100%
(100Hz)
The compressor will operate at the maximum rotation speed of 80 Hz.
2.Peak-demand control in a multiple system
The peak-demand control function is a function that restricts the maximum capacity of the units. The maximum operation
capacities of the units are restricted to specific levels relative to the maximum capacity of all units (= the compressors are
operating at the maximum rotation speed (100 Hz on the unit described in this manual)) being set as 100%.
Standard operation
The units are designed to operate in the patterns as shown below to optimize operation efficiency.
a. Maximum capacity setting (D%) ≥ 70% → All units will be operated at D Hz.
320
%
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
80%
100%
400
%
<100
%
>
Entire system
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
Entire system
Distribution of capacity
The maximum capacity of each unit is set as 100%.
(The figures in the angle brackets indicate the total
capacity in the entire system.)
b. Maximum capacity setting D% < 70% →
The number of units "N" and the capacity at which the units operate ”α" will be
determined so that either the condition (1) or (2) below is met.
1 ) D × M = 70% × (N-1) + α × 1 (40 % ≤ α < 70 % )
(N-1) units will be operated at 70 Hz, and one unit will be operated at α Hz.
200%
400
%
<100%>
400
%
<100%>
400
%
<100%>
70%
70%
60 %
0 %
2 ) D × M = α× N
70% ≤ α, The α value will be set to a value as close to 70 Hz as possible.
N units will be operated at α Hz.
200%
70%
70%
70 %
α :30% < 40 %
Re-distribution of capacity
Re-distribution of capacity
Re-distribution of capacity
Re-distribution
of capacity
Nomenclature
note. During the heating season, the unit will
not be operated at 100 Hz to save
energy consumption in the first place,
so the unit's performance may not be
affected even if the maximum capacity
setting is changed.
D %
Maximum capacity setting:
The capacity of the system when all units are operated at 100 Hz will be set as 100%.
M
Total number of units
N
No. of units in operation (calculated value)
α % ( α Hz)
Operating capacity (calculated value)
80%
80%
80 %
0%
240%
80%
Preset value
<80
%
>
Preset value
<50%>
Preset value
<50%>
Preset value
<60%>
Preset value
Содержание CAHV-P500YA-HPB
Страница 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Страница 7: ...CONTENTS HWE10060 GB ...
Страница 9: ... 2 HWE10060 GB ...
Страница 19: ... 12 HWE10060 GB ...
Страница 37: ... 30 HWE10060 GB ...
Страница 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Страница 47: ... 40 HWE10060 GB ...
Страница 55: ... IV Remote Controller 48 HWE10060 GB ...
Страница 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Страница 57: ... 50 HWE10060 GB ...
Страница 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Страница 62: ... 55 HWE10060 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 57 2 Principal Parts and Functions 58 ...
Страница 63: ... 56 HWE10060 GB ...
Страница 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Страница 69: ... 62 HWE10060 GB ...
Страница 101: ... VII Control 94 HWE10060 GB ...
Страница 103: ... 96 HWE10060 GB ...
Страница 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Страница 111: ... 104 HWE10060 GB ...
Страница 155: ... IX Troubleshooting 148 HWE10060 GB ...
Страница 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Страница 157: ... 150 HWE10060 GB ...
Страница 159: ... X Attachments 152 HWE10060 GB ...