GB
Bypass Control
-5- Outdoor unit fan
The fan's rotation speed will be controlled to approximate the values in the table below that are obtained based on the outside
temperature and the low pressure.
(Pressures and temperatures will be monitored, and the fan frequency will change accordingly in three steps.)
Compressor Frequency Control
-6- Injection LEV
Operating range of the LEV
Opening range: 50-480 (fully open)
LEV operation speed
Open 133 plus/sec
Close 200 plus/sec
At startup
For one minute after startup, the valve will be fixed to Initial Setting 1.
Between one and five minutes after startup, the valve will be fixed to Initial Setting 2.
During operation
Five or more minutes after startup, LEV2 (Injection LEV) opening will be controlled every 30 seconds to approximate the dis-
charge SH to the target value according to the changes in high pressure and discharge gas temperature.
(Refer to the table below for the target discharge SH values.)
Fan rotation
speed (rpm)
Frequency (Hz)
Outdoor temp.(A)
(°C)
Fan rotation
speed (rpm)
Frequency
(Hz)
Outdoor temp.(A)
(°C)
270
31
37 < A
≤
40
450
50
12 < A
≤
17
300
34
32 < A
≤
37
490
55
7 < A
≤
12
330
37
27 < A
≤
32
550
60
2 < A
≤
7
370
41
22 < A
≤
27
600
66
0 < A
≤
2
410
45
17 < A
≤
22
670
73
A
≤
0
Target discharge SH (Item code c31: Discharge gas temp. - discharge pressure saturation temperature)
Refer to Chapter IX [1] 2. "Checking the sensor status."
Outlet water temperature (B) (°C)
Outside temp.(A) (°C)
≤
-20
-20< A
≤
-17
-17< A
≤
-14
-14< A
≤
-11
-11< A
≤
-8
B
≤
45
20-35*
20-35*
20-35*
20-35*
35
45 < B
≤
50
20-30*
20-30*
20-30*
20-30*
30
50 < B
≤
55
20-25*
20-25*
20-25*
20-25*
25
55 < B
≤
60
20
20
20
20
20
60 < B
≤
65
20
20
20
20
20
65 < B
20
20
20
20
20
Outlet water temperature (B) (°C)
Outside temp.(A) (°C)
-8< A
≤
-5
-5< A
≤
-2
-2< A
≤
1
1< A
≤
5
5< A
B
≤
45
40
45
50
55
close
45 < B
≤
50
35
40
45
50
close
50 < B
≤
55
30
35
40
45
close
55 < B
≤
60
25
30
35
40
close
60 < B
≤
65
23
26
30
35
close
65 < B
20
23
27
32
close
*The target discharge SH will vary, depending on the operating frequency of the compressor.
Содержание CAHV-P500YA-HPB
Страница 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Страница 7: ...CONTENTS HWE10060 GB ...
Страница 9: ... 2 HWE10060 GB ...
Страница 19: ... 12 HWE10060 GB ...
Страница 37: ... 30 HWE10060 GB ...
Страница 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Страница 47: ... 40 HWE10060 GB ...
Страница 55: ... IV Remote Controller 48 HWE10060 GB ...
Страница 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Страница 57: ... 50 HWE10060 GB ...
Страница 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Страница 62: ... 55 HWE10060 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 57 2 Principal Parts and Functions 58 ...
Страница 63: ... 56 HWE10060 GB ...
Страница 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Страница 69: ... 62 HWE10060 GB ...
Страница 101: ... VII Control 94 HWE10060 GB ...
Страница 103: ... 96 HWE10060 GB ...
Страница 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Страница 111: ... 104 HWE10060 GB ...
Страница 155: ... IX Troubleshooting 148 HWE10060 GB ...
Страница 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Страница 157: ... 150 HWE10060 GB ...
Страница 159: ... X Attachments 152 HWE10060 GB ...