IX
Troubleshooting ]
- 121 -
HWE10060
GB
*1.
The codes in the parentheses in the "Error code" (PCB/RC) column indicate error detail codes.
*2.
If a error occurs, error codes shown above will blink in the 4-digit digital display on the PCB and on the remote controlle
r. (Unit address and error code will blink alternately on the remote controller display.)
*3.
Definition of symbols in the "Error reset" column
Errors that can be reset regardless of the switch settings
Errors that cannot be reset if the remote reset setting on the unit is set to "Enable" (factory setting)
Errors that cannot be reset if the remote reset setting on the unit is set to "Disable"
Errors that cannot be reset
Errors that will be automatically cancelled once its cause is removed
*4.
Power failure will be detected as an error only when the "Automatic recovery after power failure" setting on the unit is se
t to "Disable."
( The default setting for the "Automatic recovery after power failure" setting is "Enable." )
*5.
Depending on the system configuration, if transmission power supply board fault lasts for 10 minutes or longer, units will
make an abnormal stop.
This error can be reset by turning off and then back on the unit's power.
*6.
This error code will appear when multiple errors occur that are reset in different ways and when one or more of these error
s have not been reset.
This error can be reset by turning off and then back on the unit's power.
*7.
Before resetting this error, remove its causes.
Resuming operation without removing the causes of heat exchanger freeze up will cause heat exchanger damage.
Transmission line power supply PCB fault
Communication error between the main and
sub units (Multiple system mode)
*5
●Communication error due to external noise interference
●Broken wiring to the transmission power supply circuit
board (between the main and sub units)
6600
6602
●Transmission power supply PCB communication circuit
fault
6603
6606
●Broken M-NET line
6607
6608
*Preliminary error codes will not appear on the 7-segment LED.
Error Type
Cause
(problem with the installation
environment/setting error)
Cause
(component problem)
Error Code
Circuit board
Remote controller
Resetting the error
Unit side
(Circuit
board)
Remote
SWS1
Operation SW
Содержание CAHV-P500YA-HPB
Страница 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Страница 7: ...CONTENTS HWE10060 GB ...
Страница 9: ... 2 HWE10060 GB ...
Страница 19: ... 12 HWE10060 GB ...
Страница 37: ... 30 HWE10060 GB ...
Страница 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Страница 47: ... 40 HWE10060 GB ...
Страница 55: ... IV Remote Controller 48 HWE10060 GB ...
Страница 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Страница 57: ... 50 HWE10060 GB ...
Страница 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Страница 62: ... 55 HWE10060 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 57 2 Principal Parts and Functions 58 ...
Страница 63: ... 56 HWE10060 GB ...
Страница 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Страница 69: ... 62 HWE10060 GB ...
Страница 101: ... VII Control 94 HWE10060 GB ...
Страница 103: ... 96 HWE10060 GB ...
Страница 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Страница 111: ... 104 HWE10060 GB ...
Страница 155: ... IX Troubleshooting 148 HWE10060 GB ...
Страница 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Страница 157: ... 150 HWE10060 GB ...
Страница 159: ... X Attachments 152 HWE10060 GB ...