1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-6
MITSUBISHI ELECTRIC 1100 SERIES UPS
4.
CAUTION - Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to the skin and eyes. It may be toxic.
5.
CAUTION - A battery can present a risk of electrical shock and high
short circuit current. The following precautions should be observed
when working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source prior to connecting or
disconnecting battery terminals.
D) External Battery (10kVA, 20kVA, 30kVA, 40kVA and 50kVA)
Please refer to the following when installing and maintaining batteries:
1.
The customer shall refer to the battery manufacturer's installation
manual for battery installation and maintenance instructions.
2.
The maximum permitted fault current from the remote battery supply
and the DC voltage rating of the battery supply over-current
protective device are shown in Table 3.5.
Table 3.5
Maximum Permitted Fault Current
UPS Capacity
(kVA)
DC Voltage
Rating (V)
Maximum Fault
Current Permitted (A)
10 288
25,000
20 288
25,000
30 288
25,000
40 288
25,000
50 288
25,000
E) Installing Air Filter
1. Remove Front Cover
2. Grip the air filter using three ledges
Filter Size: 16W x 4.3H x 0.8D (in)
3. Close the front cover.
WARNING