1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-7
MITSUBISHI ELECTRIC 1100 SERIES UPS
This UPS does not include an AC input circuit breaker (MCCB) to protect the
bypass and main input circuit. The AC input circuit breaker (MCCB) is to
be field supplied and installed. Recommended circuit breaker (MCCB)’s
specifications are as follows:
Table 1.2 Rating of AC input circuit breaker
Capacity (kVA)
Input Voltage
(VAC)
Maximum AC Input
Rating (AAC)
Recommended
Breaker (A)
10 208 30 40
20 208 60 80
30 208 90 110
40 208 120 150
50 208 150 200
AC input and AC output over current protection and disconnect devices shall be field
supplied and installed. DC output over current protection and disconnect device shall be
field supplied and installed.