1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-18
MITSUBISHI ELECTRIC 1100 SERIES UPS
Table 1.5
Detail of Specifications
* In case of Battery Built-in Cabinet model.
Type
UP1133A-A103SU-2
UP1133A-B103SU-2
UP1133A-A203SU-2
UP1133A-B203SU-2
UP1133A-B303SU-2
UP1133A-B403SU-2
UP1133A-B503SU-2
Rated Output kVA
10
20
30
40
50
Rated Output kW
9
18
27
36
45
AC INPUT CHARACTERISTICS
Configuration
3-phase, 4-wire, plus ground
Voltage
120/208 V +15% ~ -30%
Frequency
60 Hz +/- 10%
Reflected Current THD 4% typical at 100% load; 7% typical at 50% load
BATTERY
Type VRLA
Ride Through
(at 100% load)
18min. *
5min. *
Nominal Voltage
288 Vdc
Minimum Voltage
240 Vdc
Number of Cells
144 cells
AC OUTPUT
Configuration
3-phase, 4-wire
Voltage
120/208 V
Voltage Stability
+/-1%
Frequency
60 Hz
Frequency Stability
+/-0.01% in free running mode
Power Factor
0.9 nominal
Power Factor range
0.9 ~ 1.0 lagging (within output kW rating)
Voltage THD
2% typical THD at 100% linear load
5% typical THD at 100% non-linear load
Transient Response
+/-3% typical at 100% load step
+/-1% typical at loss/return of AC power
+/-5% typical at load transfer to/from static bypass
Transient Recovery
16.7 ms
Voltage Unbalance
2% typical at 100% unbalanced load
Phase Displacement
1deg. typical at 100% load
Inverter Overload
125% for 60 seconds, 150% for 30 seconds
System Overload
1000% for 1 cycle (with bypass available)
Crest Factor Capabilities
2.5 : 1
ENVIRONMENTAL
Cooling
Forced Air
Operating
Temperature
32 deg F ~ 104 deg F (0 deg C ~ 40 deg C).
Recommended 59 deg F ~ 77 deg F (15 deg C ~ 25 deg C)
Relative Humidity
5% ~ 95% Non Condensing
Altitude
0 ~ 7400 feet. (0 ~ 5000 feet No De-rating at 40 deg C)
Location
Temperature-controlled, indoor area free of conductive contaminants
Paint Color
Munsell N1.5 (Black)