1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
2-11
MITSUBISHI ELECTRIC 1100 SERIES UPS
Refer to Figure 2.24 for a typical wiring configuration. Although this figure applies to the
remote start/stop terminals, the same wiring arrangement is used for emergency stop;
power demand; and battery temperature high.
Figure 2.24
Remote "Start" Contact Connections
Details of input contacts for remote access : IOAU-12
Terminals 3 to 4
"Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped
.
NOTE: The UPS is equipped with a selectable input contact item.
The above items are the default settings. MITSUBISHI ELECTRIC
POWER PRODUCTS, INC for setup information.
CAUTION: In all cases, a switch having a protective cover is
recommended in order to reduce the possibility of
accidental operation.
CAUTION
Relay Coil current: 10mA
Switches Only
Start
Use Momentary
UPS Cabinet
External to
UPS Cabinet
Relay
Coil
24 VDC
Start
Switch
Common
0.5S - 4S
ON
OFF
User supplied