1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-4
MITSUBISHI ELECTRIC 1100 SERIES UPS
3.4 INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to Table 3.3.1 and 3.3.2 for list of UPS weights:
Table 3.3.1
List of UPS weights (Battery Built-in Cabinet model)
UPS Capacity (kVA)
10
20
Weight (lb.)
683 *
728 *
* : Include Batteries
Table 3.3.2
List of UPS weights (Standard Cabinet model)
UPS Capacity (kVA)
10
20
30
40
50
Weight
(lb.) 313 357 375 419 463
B) Minimum clearance required for ventilation
Right side
1.0" (25 mm) (not required when sidecars are used)
Left side
1.0" (25 mm) (not required when sidecars are used)
Back side
8.0" (203 mm) (refer to Figure 3.4 for Battery Built-in Cabinet Model)
Top side
16.0" (406 mm)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
31.5" (800 mm)
Sides
1.0" (25 mm)
Rear
8.0" (203 mm)
Top side
16.0" (406 mm)
Figure 3.3
Clearance for ventilation and maintenance
!
NOTE
16" (406mm)
For Air exhaust
and Maintenance
31.5" (800mm)
For Maintenance
8" (203mm)
For Air exhaust
Side View