FA-200 Series Installation and Operation Manual
41
Appendix D: Power Supply & Battery Calculations
Use the form below to determine the required main chassis and secondary power supply (batteries).
Total Current Requirement
ALARM (
B
)______ Amps.
Battery Capacity Requirement
(
[STANDBY (
A
) ______ ] X [(24 or 60 Hours) ___ ]
)
+
(
[ALARM (
B
) ______ ] X [
♣
Alarm in Hr.] _____
)
= (
C
) ______AH
* Assuming three initiating circuits in alarm.
♣
Use
0.084
for five minutes of alarm or
0.5
for thirty minutes of alarm as a multiplier figure.
♦
Using the
MIR-425/U
2-wire smoke detector. See
Appendix A
on page 33 for other available smoke detectors.
Total Alarm Current
• Must be 2.75 amperes or less for FA-201, FA-202, and FA-204. Indicating Circuits not to exceed 2.4 amperes.
• Must be 6 amperes or less for FA-204E. Indicating Circuits not to exceed 5 amperes.
Battery Selection
• Multiply (C) by 1.20 to derate battery.
• Use BA-1065(6.5AH) Batteries for the FA-201, FA-202, and FA-204 which charges up to 12 AH Batteries.
• Use BA-110(10AH) Batteries for the FA-204E.
• The FA-204E will charge up to 24AH batteries if they are in an external Mircom BC-160 Battery Cabinet.
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated
continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt
insulation and proper over-current circuit protection that complies with the local codes. Refer to
Appendix C
on page 38 for specifications.
Power Requirements (All currents are in amperes)
Model
Number
Description
Qt
y
Standby
Total
Standby
Alarm
Total
Alarm
FA-201, FA-
202, FA-204,
FA-204E
Fire Alarm
Control Panel
X
0.110
=
0.220
=
DM-204
Zone Adder
Module
X
0.045
=
0.120
=
RM-204/RM-
208
Relay Module
X
0.005
=
0.160
=
PR-100
Polarity Reversal
and City Tie
Module
0.035
=
0.300
=
DACT-100A
DACT/Dialler
Module
0.045
=
0.120
=
RAM-208
Remote
Annunciator
0.035
=
0.090
=
RTI-1
Remote Trouble
Indicator
0.035
=
0.035
=
Two-Wire Smoke Detectors
♦
0.0001
=
* 0.090
= 0.090
Four-Wire Smoke Detectors
X
=
=
Signal Load (bells, horns,
strobes, and etc.)
=
Auxiliary Power Supply for Remote Annunciators
Alarm
=
Total currents (Add above currents)
STANDBY
(
A
)
(
B
)