Appendix A: Compatible Devices
34
Underwriter’s Labs Inc. (UL) United States: Two-Wire Smoke Detector Control Panel
Compatibility
Notes:
• Whether mixing different models of compatible smoke detectors or using the same model on the same
circuit, total standby current of all detectors must not exceed 3 mA.
• The below listed smoke detectors are compatible with initiating circuits having Compatibility Identifier
"A".
Smoke
Detector Make
Model / Base
Compatibility
Identifier Head
/ Base
Rated
Standby
Current
Smoke Detector Make
Model / Base
Compatibilit
y Identifier
Head / Base
Rated
Standby
Current
Hochiki
System Sensor (cont’d)
DCD-135/NS6-
220
HD-3/HB-72
0.035mA
2400AIT
A - N/A
0.12 mA
DCD-135/NS4-
220
HD-3/HB-3
0.035mA
2451 / B401B
A - A
0.12 mA
DCD-135/HSC-
220R
HD-3/HB-3
0.035mA
2451 / B406B
A - A
0.12 mA
DCD-190/NS6-
220
HD-3/HB-3
0.035mA
2451 / DH400
A - N/A
0.12 mA
DCD-190/NS4-
220
HD-3/HB-3
0.035mA
2451TH / B406B
A - A
0.12 mA
DCD-190/HSC-
220R
HD-3/HB-3
0.035mA
2451 / B401
A - A
0.12 mA
SIJ-24/NS6-220
HD-3/HB-72
0.040mA
2451TH / B401
A - A
0.12 mA
SIJ-24/NS4-220
HD-3/HB-3
0.040mA
4451HT / B401B
A - A
0.12 mA
SIJ-24/HSC-
220R
HD-3/HB-3
0.040mA
4451HT / B406B
A - A
0.12 mA
SLR-24/NS6-220
HD-3/HB-72
0.045mA
4451HT / B401
A - A
0.12 mA
SLR-24/NS4-220
HD-3/HB-3
0.045mA
5451 / B401B
A - A
0.12 mA
SLR-24/HSC-
220R
HD-3/HB-3
0.045mA
5451 / B401
A - A
0.12 mA
SLR-24H/NS6-
220
HD-3/HB-3
0.045mA
5451 / B406B
A - A
0.12 mA
SLR-24H/NS4-
220
HD-3/HB-3
0.045mA
SLR-24H/HSC-
220R
HD-3/HB-72
0.045mA
SLR-835/NS6-
220
HD-3/HB-3
0.045mA
Sentrol - ESL
SLR-835/NS6-
220
HD-3/HB-3
0.045mA
429C
S10A - N/A
0.10 mA
SLR-835/NS4-
220
HD-3/HB-3
0.045mA
429CT
S10A - N/A
0.10 mA
SLR-835/HSC-
220R
HD-3/HB-72
0.045mA
429CST
S11A - N/A
0.10 mA