FA-200 Series Installation and Operation Manual
21
System Checkout
Before Turning The Power On...
1. To prevent sparking,
do not connect
the batteries. Connect the batteries after powering the system from the
main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged-in properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to Earth Ground (cold water pipe).
8. Make sure to
close the front cover plate
before powering the system from main AC supply.
Power-up Procedure
1. After completing the System Checkout procedures, power-up the panel. The "AC-ON" green LED should illu-
minate, the “Common Trouble” LED should illuminate, and the buzzer should sound.
2. Press the System Reset button. Since the batteries are not connected, the "Battery Trouble" LED should
illuminate, and the buzzer should sound intermittently, and the Common Trouble LED should flash.
3. Connect the batteries while observing correct polarity; the red wire is positive (+) and black wire is negative (-).
All indicators should extinguish except for normal power "AC-ON" green LED.
4. Configure the fire alarm control panel as described in the
System Configuration
section on page 28.
Troubleshooting
Message
Description
Circuit Trouble
Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated,
as well as the Common Trouble indicator and Trouble buzzer. To correct the fault, check for
open wiring on that particular circuit loop or see if the circuit disconnect switch is in the ON
or CLOSED position.
Note: disconnecting a circuit will cause a system trouble (off-normal
position).
Remote Fail
The panel will display a Remote Fail for any failure reported by, or failure to communicate
with a remote annunciator, DACT-100A, or PR-100.
Ground Fault
The FA-200 panel has a Common Ground Fault Detector. To correct the fault, check for any
external wiring touching the chassis or other earth ground connection.
Battery Trouble
Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will
cause a battery trouble. If battery trouble condition persists, replace the batteries as soon
as possible.