FA-200 Series Installation and Operation Manual
9
Module Settings
Main Fire Alarm Module
Class A / B Selection
On the FA-202, FA-204 and FA-204E only, JW1 & JW2 are connected from 1 to 2 for initiating circuit Class B (Style
B) operation, and from 2 to 3 for Class A (Style D) operation. These are not present on the FA-201, and only JW2 is
present on the FA-202.
Zone Adder Module:
On an FA-204E only, remove the jumper on
JW4
if a DM-204 Zone Adder Module is installed.
The zone adder module is plugged into P6 & P7.
Relay Module:
Remove the jumper on
JW3
if an RM-204 or RM-208 Relay Module is installed. The relay module is
plugged into P1.
Digital Communicator:
Remove the jumper on
JW6
if a DACT-100A Digital Communicator is installed. The digital
communicator is plugged into P8.
City Tie:
Remove the jumper on
JW6
if a PR-100 City Tie is installed. The City Tie is plugged into P8.
Battery:
Connected to P2(+) & P3(-) via the factory installed cables.
Transformer:
Factory wired to P4 & P5, do not disconnect.
JW5:
There should be no jumper here; do not use.
SW9,11,13:
Configuration DIP switches.
Battery Fuse F1:
Replace with 10 amp, 1-1/4" fast acting fuse.
Figure 5: Main Fire Alarm Module
Note:
The Class A/B selection affects all initiating circuits, and must be used with the correct Configuration
DIP switch setting.
P6
F1
10 AMP
BATTERY
FUSE
SW13
1
2
3
JW2
P3
2
3
1
BATT+
P4
P5
P2
BATT-
XMFR
XMFR
JW1
P7
P8
JW4
JW5
JW3
JW6
SW11
SW9
P1
SUPV RLY
COM-
COM+
S
IND2-IND2-
IND1- IND1- IND1+ IND1+ INI4- INI4+ INI3- INI3+ INI2- INI2+ INI1- INI1+
485- 485+
-
+
TRB TRL
IND2+ IND2+
NO NC COM
ALM RLY
NO NC COM
TBL RLY
4 WIRE
NO NC COM
Note:
Do not plug DACT into P1 on main
board. Plug into P8 only when system is
powered off.
Note:
Do not plug RM-204/
208 into P8 on main board.
Plug into P1 only when
system is powered off.