Appendix C: Module Specifications And Features
40
• Auxiliary relays:
(resistive loads) common alarm, supervisory, trouble
all are Form C, 1 amp, 28VDC
• Microcontroller-based design.
• DIP switch configurable.
• Walktest function.
Electrical ratings:
• AC Line Voltage:
120V 60Hz / 240V 50Hz
1.25A
• Power supply ratings:
6 amps max. (secondary)
• For indicating circuits:
24VDC unfiltered, 5 amps max.
• Battery:
24VDC, Gel-Cell/Sealed Lead-Acid
• Charging capability: 1
0 to 24 AH batteries
• Fuse on main board:
10 Amps.
• Current consumption:
standby:
110 mA
alarm:
220 mA
DM-204 Zone Adder Module
• May be added to FA-204E.
• Four supervised Class B (Style B) or two Class A (Style D) initiating circuits; configurable. [Compatibility ID “A”]
Power limited: 22VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
• Two Class B or A (Style Y or Z ) indicating circuits; configurable as strobes or audibles.
Power limited: 24 VDC unfiltered, 1.7A @49°C per Circuit
• Current consumption:
standby
: 45 mA
alarm:
120 mA
• Eight-zone remote annunciator (RAM-208)
• RS-485 Interface, up to 3 per FA-200 Panel.
• Current consumption:
standby:
35 mA
alarm:
90 mA
• Remote trouble indicator (RTI-1)
• Trouble LED and trouble buzzer
• Current consumption:
standby:
35 mA
alarm:
35 mA
• End-of-line resistor plates (MP-300, MP-300R)
• Internal 3.9 Kohm, ½ Watt, 5% resistor.
• External battery cabinet (BC-160)
• Up to 24 A-H batteries for FA-200 panels.
System model:
FA-200 Fire Alarm Control Panel
System type:
Local, auxiliary (using PR-100), remote station protected premises (using DACT-100A or PR-100),
central station protected premises (using DACT-100A).
Type of service:
A, M, WF, SS (SS is only local or with DACT-100A)
Type of signalling:
Non-Coded
Applicable standards:
NFPA 70 and 72, UL-864, ULC S-524, ULC S-527