Indicators, Controls, & Operation
24
Controls
System Reset Switch
The System Reset momentary switch resets the fire alarm control panel and all circuits:
Signal Silence Switch
Activating the Signal Silence momentary switch when the panel is in alarm turns on the signal silence indicator and
deactivates any silenceable indicating circuits. Non-silenceable circuits are unaffected. Signals will re-sound upon
any subsequent alarm. This switch does not function during any configured Signal Silence Inhibit timer period. It
also does not function if the indicating circuits are active as the result of a fire drill.
Fire Drill Switch
The Fire Drill momentary switch activates all non-disconnected indicating circuits, but does not transmit any alarms
via the dialler, city tie, or common alarm relay, nor are any RM-204 or RM-208 relays activated. The fire drill is
cancelled by activating the switch again, or if the panel goes into a real alarm.
Auxiliary Disconnect Switch
Activating the Auxiliary Disconnect momentary switch activates the auxiliary disconnect function. Activating the
switch again de-activates the function. When auxiliary disconnect is active, common alarm and common
supervisory relays, and any RM-204 / RM-208 relays are not activated. The trouble relay is activated. If installed,
dialler or polarity reversal and city tie modules are also inactive, causing a trouble condition.
Lamp Test Switch
Activation of the Lamp Test momentary switch turns all front panel Indicators and the buzzer on.
Buzzer Silence Switch
Activation of the Buzzer Silence momentary switch while the Buzzer is sounding silences the Buzzer. The Buzzer
will resound if there is a subsequent event. Switch activation will also silence the buzzer on all attached
annunciators.
Circuit Disconnect Switches
Activation of these non-momentary switches disconnects the respective Initiating Circuit, and causes a Circuit
Trouble for that Initiating Circuit while active. If the disconnect switch is turned off (to its normal position) while there
is an Alarm condition in that circuit, the respective circuit Status LED will flash at a rate of 120 flashes per minute to
indicate a Pending Alarm, for 5 seconds. If the disconnect switch is not turned back on, an Alarm will be processed
normally.
•Resets all latching trouble conditions
•Resets all initiating circuits
•Resets four-wire smoke supply
•Turns off all indicating circuits
•Turns off Signal Silence
•Turns off Fire Drill
•Stops and resets all timers
•Processes inputs as new events
•Aux Disconnect is not affected