Determine the oxidant and sample water volumes for the 1, 3, and 5 ppm doses. Given
that MIOX OSG is still generating an oxidant concentration of 250 ppm.
1 ppm
3ppm
5ppm
Dilution Factor (X) 250/1 =
250
250/3
=
83.3
250/5
=
50
mL of Oxidant
100/250 =
0.4
100/83.3
=
1.2
100/50
=
2
mL of Sample Wate
r
100-0.4 =
99.
6 100-1.2
=
98.8
100-2
=
98
For a
1 ppm
dose,
0.4 mL
of oxidant should be mixed with
99.6 m
L of sample water For a
3 ppm
dose,
1.2 mL
of oxidant should be mixed with
98.8 mL
of sample water For a
5
ppm
dose,
2.0 mL
of oxidant should be mixed with
98 mL
of sample water
Procedure
Stagger preparation of each dilution by several minutes to allow enough time for accurate
analysis of FAC at each dilution. FAC readings should be taken at the following times: T = 0,
30 minutes, 60 minutes, and 90 minutes. Readings beyond 90 minutes are determined by
interpretation of data from the first 90 minutes.
• Accurately measure the volume (mL) of calculated sample water and place in a
glass jar.
• Accurately measure the volume (mL) of oxidant required.
• Add oxidant to sample water jar and swirl briefly to mix.
• Immediately measure and record the FAC concentration and time the reading is
taken (time = 0).
• Repeat the above steps for the other dilutions, measure each at time = 0 before
preparing the next dilution, and then take FAC readings at 30, 60, and 90 minutes.
Generate a table similar to the one given in the example below.
Example:
Fill out the table properly and completely. The oxidant solution must be diluted to 1 ppm, 3
ppm, and 5 ppm doses as determined in the previous example. The FAC residual is
measured in 30-minute intervals until the chart is filled out as below (measurements are
based on assumed tests for this example):
Sample A
(1 ppm)
Time
(o’Clock)
Sample B
(3 ppm)
Time
(o’Clock)
Sample C
(5 ppm)
Time
(o’Clock)
Содержание RIO-S Series
Страница 9: ...MIOX RIO S Series Operators Manual 102 00130 D Page 9 Figure 2 RIO S OSG Space Requirements...
Страница 30: ...MIOX RIO S Series Operators Manual 102 00130 D Page 30 Figure 13 External Plumbing Electrical Overview Rear...
Страница 37: ...MIOX RIO S Series Operators Manual 102 00130 D Page 37 Figure 19 Brine Pressure Boost System...
Страница 75: ...MIOX RIO S Series Operators Manual 102 00130 D Page 75 X mg L chlorine concentration Y gph flow...