![MIOX RIO-S Series Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/miox/rio-s-series/rio-s-series_installation-operation-and-maintenance-manual_1804803054.webp)
MIOX RIO-S Series Operators Manual
102-00130-D
Page
54
Troubleshooting
Fault Conditions
The RIO-S is preprogrammed with a number of fault conditions which trigger whenever the
system is running atypically. The faults are classified as either hard or soft faults. Hard
faults automatically shut the system down and require a power cycle to reset the system.
Soft faults try to resolve themselves and automatically restart the system a number of
times before requiring a power cycle reset.
Table 2: Fault Conditions Descriptions
Fault Name
Condition
Time
Delay
(sec)
Cell
Power
Removed
Flush
Removed
Auto
Retry
3x
Leak Detect
Liquid detected on cell
bank sensing band
near drain
2 YES YES NO
Contact Fails to Close No contact status
signal when contact
enable signal on
1 NO NO NO
Contact Fails to Open Contact status signal
on, then contact enable
signal off
5 YES NO NO
High Cell Current
Cell current greater
than 125% of target
1 YES NO YES
Low Cell Voltage
Cell voltage less than
400 V when contactor
is on
5 NO NO NO
High Oxidant Temp
Oxidant temp greater
than 150° F
10 NO
NO
NO
High Brine Pump
Voltage
Brine pump control
voltage greater than
3.75 V.
60 NO
NO
NO
High Delta Temp
Temp difference
between inlet and
outlet greater than 50°
F or less than -10° F.
45 NO
NO
NO
Oxidant or Water Side
Panel Open
(Interlock)
Panel removed with
power applied to unit
1 YES YES NO
Switchgear Cabinet
Door Open
Switchgear door
removed with power
applied to unit
1 YES YES NO
Emergency Stop
Pressed
E-STOP triggered
1
YES
YES
NO
Low Water Flow
20% decrease in water
flow rate for 45
seconds
45 YES
NO
YES
Содержание RIO-S Series
Страница 9: ...MIOX RIO S Series Operators Manual 102 00130 D Page 9 Figure 2 RIO S OSG Space Requirements...
Страница 30: ...MIOX RIO S Series Operators Manual 102 00130 D Page 30 Figure 13 External Plumbing Electrical Overview Rear...
Страница 37: ...MIOX RIO S Series Operators Manual 102 00130 D Page 37 Figure 19 Brine Pressure Boost System...
Страница 75: ...MIOX RIO S Series Operators Manual 102 00130 D Page 75 X mg L chlorine concentration Y gph flow...