10
installed all of the way into the receptacle. Upon successful
connection, verify that the bracket will not allow removal of the
connector.
For multiple battery pack installation, each battery pack is "daisy chained"
in a similar fashion, with the cable from the last battery pack connected to
the previous pack. Remove the protective strips only from the battery
connectors that you use.
NOTE: When the protective strip is removed from the XRT UPS or
the XRT Battery Pack cable and daisy-chain battery connector,
battery system voltage is present at these connector contacts
(48vdc, depending on model). Be sure the connector contacts are
covered with the protective strip when not mated with another
connector.
7. The unit is now ready for normal startup procedures as described in
the UPS owner's manual. Make sure all switches and breakers on all
units installed are placed in the ON position. Failure to have all of the
switches in the ON position may render the UPS inoperable or
reduce the runtime when multiple battery packs are installed.
STYLE 2: HARDWIRE CONFIGURATION INSTALLATION
1. Make sure the installation placement and caster removal procedures
mentioned above have been carefully followed.
2. Be sure the UPS Power switch is in the OFF position. If this model of
battery pack contains a circuit breaker, make sure the battery pack
circuit breaker is in the OFF position.
3. For installation of the battery pack connection wires, locate the
terminal block on the back of the UPS. To properly identify the
terminal block, refer to the Installation section in the UPS owner's
manual.
Содержание XRT Series
Страница 1: ...User s Manual...
Страница 17: ...17...