WARNING:

  Risk of Electrical Shock.  Hazardous live parts inside

these Battery Packs are energized from the battery.

CAUTION!  

To de-energize the Battery Pack:

1.

If the UPS is on press and release the Off/On button.

2.

Disconnect the UPS from the wall outlet.

3.

Turn off the DC breaker on the rear panel of the Battery Pack.

4.

Disconnect the battery cable from the rear panel of the UPS.

5.

To de-energize the Battery Pack completely, disconnect the bat-
teries.

CAUTION!

  These Battery Packs are intended to be install in a

temperature controlled environment that is free of conductive con-
taminants.  Select a location which will provide good air circulation for
the Battery Pack and UPS at all times.

CAUTION!  

To reduce the risk of electrical shock with the installa-

tion of these Battery Packs, with the UPS equipment and the con-
nected equipment, the user must ensure that the combined sum of
the AC leakage current does not exceed 3.5mA.

WARNING:

  

These Battery Packs contains potentially hazardous

voltages.  Do not attempt to disassemble the Battery Pack beyond
the battery replacement procedure.  These Battery Packs contains
no user serviceable parts.  Repairs and Battery replacement must be
performed by QUALIFIED SERVICE PERSONNEL ONLY.

Receiving Inspection

After removing your Battery Pack from its carton, it should be inspected for
damage that may have occurred in shipping.  Immediately notify the carrier and
place of purchase if any damage is found.  Warranty claims for damage caused
by the carrier will not be honored.  The packing materials that your Battery
Pack was shipped in are carefully designed to minimize any shipping damage.
In the unlikely case that the Battery Pack needs to be returned to the manufac-
turer, please use the original packing material.  Since the manufacturer is not
responsible for shipping damage incurred when the system is returned, the
original packing material is inexpensive insurance.

PLEASE SAVE THE PACKING MATERIALS!

English

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS !

Thank you for purchasing this power protection product.  It has been designed
and manufactured to provide many years of trouble free service.

Please read this manual before installing your Endeavor and Enterprise Plus
Series Battery Pack, models BP24RTEXL, BP48RTEXL,  BP36RTEXL,
BP72RTEXL as it provides important information that should be followed during
installation and maintenance of the Battery Packs and batteries allowing you
to correctly set up your system for the maximum safety and performance.
Included is information on customer support and factory service if it is required.
If you experience a problem with the Battery Packs please refer to the Trouble-
shooting guide in this manual to correct the problem or collect enough informa-
tion so that the Technical Support Department can rapidly assist you.

This symbol indicates "ATTENTION"

This symbol indicates "Risk of Electrical Shock"

This symbol indicates "Direct Current Supply"

This symbol indicates "Equipment Grounding Conductor"

1. INTRODUCTION

Содержание BP24RTEXL

Страница 1: ... s Manual Rack Tower Extended Runtime Battery Packs Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com P N 34000424 ...

Страница 2: ... Copyright 2011 English 1 Introduction 2 2 Controls and Indicators 6 3 Installation 7 4 Replacing the Battery 12 5 Obtaining Service 16 6 Specifications 17 7 Limited Product Warranty 18 TABLE OF CONTENTS ...

Страница 3: ...nd place of purchase if any damage is found Warranty claims for damage caused by the carrier will not be honored The packing materials that your Battery Pack was shipped in are carefully designed to minimize any shipping damage In the unlikely case that the Battery Pack needs to be returned to the manufac turer please use the original packing material Since the manufacturer is not responsible for ...

Страница 4: ... where failure or malfunction of the product can be reason ably expected to cause failure of the life support device or to significantly affect its safety or effectiveness We do not recommend the use of any of our prod ucts in direct patient care We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that a the risks of inju...

Страница 5: ...he Battery Pack Place the Battery Pack in the final desired location and complete the rest of the installation procedure WARNING These Battery Packs are extremely heavy Any time the Battery Pack has to be handled be sure to use enough person nel strong supports and equipment to safely handle the Battery Pack ENVIRONMENTAL Operating Temperature max Operating Storage Humidity Operating Elevation 0 t...

Страница 6: ... mounting brackets and rails for the standard 19 46 5cm 4 post rack The screws for mounting the Battery Pack to the rack are not included screw size varies with rack size 1 Mount the rails to the 4 post rack FIG 1 2 Locate the mounting bracket screw holes on the side panels of the Battery Pack at the front of the Battery Pack FIG 2 3 Align the mounting bracket with the mounting bracket screw holes...

Страница 7: ...us voltage for the Battery Packs CONNECTING THE BATTERYPACK QUALIFIED SERVICE PERSONNELONLY NOTE When using these Battery Packs the UPS must be configured so that the UPS will report the correct estimated runtime in the SentryPlus software or the SNMP card and to make the Battery capacity bar graph LEDs display properly See the SentryPlus software or the SNMP NET card User s Manual to configure th...

Страница 8: ...e operated vents These Battery Packs contain sealed non spillable maintenance free lead acid batteries CAUTION Yuasa Part REW45 12 CSB Part HR 1234W F2 18 12V9 0Ah English WARNING This Battery Pack contains potentially hazardous voltages Do not attempt to disassemble the Battery Pack beyond the battery replacement procedure These Battery Packs contain no user serviceable parts Repairs and Battery ...

Страница 9: ...d and black NOTE Some sparking might occur this is normal 31 Re install the battery retaining bracket FIG 5 32 Re install the retaining screws for the battery retaining bracket FIG 5 33 Re install the front panel on the Battery Pack 34 Re install the front panel retaining screws FIG 6 35 Re install the front panel retaining screw cover plates FIG 7 36 Reconnect all of the external battery cables 3...

Страница 10: ...972 446 9011 or visit our Web site at www minutemanups com the Discussion Board Please have the following information available BEFORE calling the Technical Sup port Department A Your name and address B Where and when the unit was purchased C All of the model information about your Battery Pack and UPS D Any information on the failure including LEDs that may be illuminated E A description of the p...

Страница 11: ...fter delivery in regard to use or application of Para Systems s equipment is furnished without charge and on the basis that it represents Para Systems s best judgment under the circumstances but it is used at the recipient s sole risk EXCEPTAS PROVIDED HEREIN PARA SYSTEMS MAKES NO WARRANTIES EX PRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some sta...

Отзывы: