21.  Remove the old batteries from the bottom half of the plastic battery tray.
22.  Install the new batteries into the bottom half of the plastic battery tray in the
      same position as the original batteries.
23.  Verify proper polarity.  Re-install the battery jumper wires on the new
       batteries.
24.  Verify proper polarity.  Reconnect the battery negative (black) wires.
25.  Verify proper polarity.  Reconnect the battery positive (red) wires.
26.  Install top half of the plastic battery tray onto the batteries.
27.  Tape the battery module together.
28.  Slide the battery modules into the Battery Pack.
29.  Secure the battery cables with the battery cable ties.
30.  Verify proper polarity.  Reconnect the battery connectors (red and black).
NOTE:  Some sparking might occur, this is normal.
31.  Re-install the battery retaining bracket. (FIG. 5)
32.  Re-install the retaining screws for the battery retaining bracket. (FIG. 5)
33.  Re-install the front panel on the Battery Pack.
34.  Re-install the front panel retaining screws. (FIG. 6)
35.  Re-install the front panel retaining screw cover plates. (FIG. 7)
36.  Reconnect all of the external battery cables.
37.  Turn on all of the DC circuit breakers on the rear panel of all of the Battery
      Packs.
38.  Properly dispose of the old batteries at an appropriate recycling facility or
       return them to the supplier in the packing material for the new batteries.
39.  The Battery Pack is ready for normal operation.
NOTE:  If the UPS has a Weak/Bad Battery Alarm after replacing the batteries,
the user must initiate a self test to clear the Weak/Bad Battery Alarm.  To
initiate a self test see section 4 "SELF TEST" in the UPS's User's Manual.

FIG. 1

FIG. 5

FIG. 6

FIG. 7

Содержание BP24RTEXL

Страница 1: ... s Manual Rack Tower Extended Runtime Battery Packs Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com P N 34000424 ...

Страница 2: ... Copyright 2011 English 1 Introduction 2 2 Controls and Indicators 6 3 Installation 7 4 Replacing the Battery 12 5 Obtaining Service 16 6 Specifications 17 7 Limited Product Warranty 18 TABLE OF CONTENTS ...

Страница 3: ...nd place of purchase if any damage is found Warranty claims for damage caused by the carrier will not be honored The packing materials that your Battery Pack was shipped in are carefully designed to minimize any shipping damage In the unlikely case that the Battery Pack needs to be returned to the manufac turer please use the original packing material Since the manufacturer is not responsible for ...

Страница 4: ... where failure or malfunction of the product can be reason ably expected to cause failure of the life support device or to significantly affect its safety or effectiveness We do not recommend the use of any of our prod ucts in direct patient care We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that a the risks of inju...

Страница 5: ...he Battery Pack Place the Battery Pack in the final desired location and complete the rest of the installation procedure WARNING These Battery Packs are extremely heavy Any time the Battery Pack has to be handled be sure to use enough person nel strong supports and equipment to safely handle the Battery Pack ENVIRONMENTAL Operating Temperature max Operating Storage Humidity Operating Elevation 0 t...

Страница 6: ... mounting brackets and rails for the standard 19 46 5cm 4 post rack The screws for mounting the Battery Pack to the rack are not included screw size varies with rack size 1 Mount the rails to the 4 post rack FIG 1 2 Locate the mounting bracket screw holes on the side panels of the Battery Pack at the front of the Battery Pack FIG 2 3 Align the mounting bracket with the mounting bracket screw holes...

Страница 7: ...us voltage for the Battery Packs CONNECTING THE BATTERYPACK QUALIFIED SERVICE PERSONNELONLY NOTE When using these Battery Packs the UPS must be configured so that the UPS will report the correct estimated runtime in the SentryPlus software or the SNMP card and to make the Battery capacity bar graph LEDs display properly See the SentryPlus software or the SNMP NET card User s Manual to configure th...

Страница 8: ...e operated vents These Battery Packs contain sealed non spillable maintenance free lead acid batteries CAUTION Yuasa Part REW45 12 CSB Part HR 1234W F2 18 12V9 0Ah English WARNING This Battery Pack contains potentially hazardous voltages Do not attempt to disassemble the Battery Pack beyond the battery replacement procedure These Battery Packs contain no user serviceable parts Repairs and Battery ...

Страница 9: ...d and black NOTE Some sparking might occur this is normal 31 Re install the battery retaining bracket FIG 5 32 Re install the retaining screws for the battery retaining bracket FIG 5 33 Re install the front panel on the Battery Pack 34 Re install the front panel retaining screws FIG 6 35 Re install the front panel retaining screw cover plates FIG 7 36 Reconnect all of the external battery cables 3...

Страница 10: ...972 446 9011 or visit our Web site at www minutemanups com the Discussion Board Please have the following information available BEFORE calling the Technical Sup port Department A Your name and address B Where and when the unit was purchased C All of the model information about your Battery Pack and UPS D Any information on the failure including LEDs that may be illuminated E A description of the p...

Страница 11: ...fter delivery in regard to use or application of Para Systems s equipment is furnished without charge and on the basis that it represents Para Systems s best judgment under the circumstances but it is used at the recipient s sole risk EXCEPTAS PROVIDED HEREIN PARA SYSTEMS MAKES NO WARRANTIES EX PRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some sta...

Отзывы: