21. Remove the old batteries from the bottom half of the plastic battery tray.
22. Install the new batteries into the bottom half of the plastic battery tray in the
same position as the original batteries.
23. Verify proper polarity. Re-install the battery jumper wires on the new
batteries.
24. Verify proper polarity. Reconnect the battery negative (black) wires.
25. Verify proper polarity. Reconnect the battery positive (red) wires.
26. Install top half of the plastic battery tray onto the batteries.
27. Tape the battery module together.
28. Slide the battery modules into the Battery Pack.
29. Secure the battery cables with the battery cable ties.
30. Verify proper polarity. Reconnect the battery connectors (red and black).
NOTE: Some sparking might occur, this is normal.
31. Re-install the battery retaining bracket. (FIG. 5)
32. Re-install the retaining screws for the battery retaining bracket. (FIG. 5)
33. Re-install the front panel on the Battery Pack.
34. Re-install the front panel retaining screws. (FIG. 6)
35. Re-install the front panel retaining screw cover plates. (FIG. 7)
36. Reconnect all of the external battery cables.
37. Turn on all of the DC circuit breakers on the rear panel of all of the Battery
Packs.
38. Properly dispose of the old batteries at an appropriate recycling facility or
return them to the supplier in the packing material for the new batteries.
39. The Battery Pack is ready for normal operation.
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries,
the user must initiate a self test to clear the Weak/Bad Battery Alarm. To
initiate a self test see section 4 "SELF TEST" in the UPS's User's Manual.