42
Se
tti
ng
o
f F
un
ct
io
n
6-10. Change of data stored place
The data stored place of [Internal RAM] or [EEPROM] is selected by C function CF-17.
Setting range
:
000
~
111
:
100
0
:
Internal RAM
1
:
EEPROM
* Each digit of the set value corresponds to the following items, and selects stored place of
each digit.
10
0
digit : ZERO set data,
10
1
digit : Tare weight cancellation data
10
2
digit : Set data of simple comparator mode and 5 steps comparator mode
Ex) Setting value
:
001 -> ZERO set data is stored at [EEPROM], and set data of tare weight
cancellation, simple comparator mode and 5 steps comparator mode is stored at [Internal
RAM]
6-11.Stability detection while setting
[VALID] or [INVALID] of stability detection while setting the S function and various
measurement mode is selected by C function CF-20.
Setting range
:
0,1
0
:
INVALID
1
:
VALID
6-12.Gravity acceleration compensation
When the calibration place and the using place of the measuring are different, the error is
caused in span by the difference of the gravity acceleration of the various place districts. The
gravity acceleration compensation function is a function for the compensation of this span
error by setting the gravity acceleration of two districts with a different calibration place and
using place. When the calibration place and the using place are the same, it is not necessary
to execute the gravity
acceleration compensation.
6-12-1. Setting method of gravity acceleration compensation
The setting method of the gravity acceleration compensation is selected by C function CF-
25.
Selectable range
:
0,1
0
:
The district number is set.
1
:
The numerical value of gravity acceleration is set.
•
Please refer to [12. Memorized place of set data] for the stored place of data other
than the above.
•
The data stored at [Internal RAM] is not backed up.
•
Please set the stored place to [Internal RAM] when the set data is continuously
changed, and the rewritable time of [EEPROM] might exceed about on million times.
•
Please do not change in the set value under the measurement because the A/D
sampling rate decreases temporarily while rewriting the set value when the stored
place of set data is [EEPROM]. Please set the stored place to [Internal RAM] if you
change the set value under the measurement.