Switch setting
PR 5500-1
Switch setting
PR 5500-2
Switch setting
PR 5500-3
Coniguration
ON: -
OFF: S1…S8
ON: -
OFF: S1…S8
ON: S1
OFF: S2…S8
[Operating] - [System setup] - [Connected
devices] - [PC via EW-Com] - [Interface] -
[Option 1 RS
‑
485-A]
4.5.1.5
Connecting an IS platform via RS
‑‑
485 (2-wire)
Using this optional card, it is possible to connect an IS platform with xBPI or SBI protocol.
Note:
Only one platform can be supplied power from the PR 5500 and the weighing
electronics board PR 5500/10 must not be plugged in.
Example:
PR 5500/04
PR 5500/04
RS-485-A
PR 5500
PR 5500
RxD/TxD-P
RxD/TxD-N
A-TxB
A-TxA
A-RxB
A-RxA
GNDI
+ 24 V
GND
DC
DC
1
2
3
4
5
6
7
8
↓
O
N
A
{
S4
S1
S3
S2
120
120
1K6
1K6
K
A
B
J
L
C
H
M
D
G
F
E
L
A
E
G
K
RxD - TxD - P
RxD - TxD - N
GND
A
RS-485
2
1
3
4
①
IS platform xBPI protocol (slave)
②
Half duplex
③
12-pin male connector
④
AC/DC adapter
Switch settings
PR 5500
Coniguration PR 5500
ON: S2, S3, S4
OFF: S1
[Operating] - [System setup] - [Weighing points] - [Weighing
point X] - [xBPI scale] - [Interface] - [Option x RS-485-A]
4 Device installation
Process Controller Maxxis 4 PR 5500
Minebea Intec
EN-41