TYPICAL SHARP-CRESTED WEIRS
Rectanglar - suppressed
U3 = 1.5
Trapezoidal (Cipolletti)
U3 = 1.5
Sutro (Proportional)
U3 = 1
(symmetrical or asymmetrical)
Q
minimum
3
h
max
h
transducer location
Typical Weir Installation
V - notch or Triangular
U3 = 2.5
For rated flows under free flow conditions, the head is measured upstream of the weir plate at a minimum
distance of 3 times the maximum head (i.e. where the liquid surface is not effected by drawdown). The
minimum allowable distance from transducer to maximum liquid level is 60 cm (2 ft.)
PL-269
7 – 10