V6-i VRF 50Hz
23
P
art
2
- O
ut
do
or
Unit
Engineer
ing Da
ta
Table 2-1.2: 10/12HP specifications
HP
10
12
Model name
MVi-280WV2RN1(A)
MVi-335WV2RN1(A)
Power supply
V/Ph/Hz
380-415/3/50
Cooling
1
Capacity
kW
28.5
33.5
Power input
kW
12.23
15.30
EER
2.33
2.19
Heating
2
(Rated)
Capacity
kW
28.5
33.5
Power input
kW
7.68
10.15
COP
3.71
3.30
Heating
3
(Max.)
Capacity
kW
31.5
37.5
Power input
kW
7.87
11.72
COP
4.00
3.20
Connected indoor
unit
Total capacity
50-130% of outdoor unit capacity
Maximum quantity
16
20
Compressor
Type
DC inverter rotary
DC inverter rotary
Quantity
1
1
Oil type
RB75EA
FV50S
Start-up method
Soft start
Soft start
Fan
Type
Propeller
Motor type
DC
Quantity
2
Motor output
kW
0.17×2
0.17×2
Air flow rate
m
3
/h
11000
11300
Drive type
Direct
Refrigerant
Type
R410A
Factory charge
kg
6.5
8
Pipe connections
4
Liquid pipe
mm
Φ9.53
Φ12.7
Gas pipe
mm
Φ22.2
Φ25.4
Sound pressure level
5
dB(A)
60
61
Sound power level
5
dB(A)
78
81
Net dimensions (W×H×D)
mm
1120×1558×528
Packed dimensions (W×H×D)
mm
1270×1720×565
Net weight
kg
144
157
Gross weight
kg
160
173
Ambient Temp.
operation range
Cooling
o
C
-5~48
Heating
o
C
-20~24
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
4. Diameters given are those of the unit's stop valves.
5. Sound pressure level is measured at a position 1m in front of the unit and 1m above the floor in a semi-anechoic chamber.