50
9.3.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0)
Error Code
P0
Malfunction decision
conditions
When the voltage signal that IPM send to compressor drive chip
is abnormal, the display LED
will show “P0” and AC will turn off.
Supposed causes
●
Wiring mistake
●
IPM malfunction
●
Outdoor fan ass’y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Trouble shooting:
Check if the wiring between main
PCB and compressor connected by
error and if the wires and connectors
are broken?
Correct the connection or replace the
wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform. Refer to page 64.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
please refer to the solution of fan
speed is out of control.
Yes
Check if the compressor resistance
values are uniform .Refer to page 63.
No
Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.
Содержание Mono 3D
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MS11M 09HRFN1 MW0W MS11M 12HRFN1 MV0W MS11M 18HRFN1 MU0W...
Страница 15: ...13 MS11M 24HRDN1 MT0W...
Страница 16: ...14 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 17: ...15 MOF 18HFN1 MU0W...
Страница 18: ...16 MOG 24HFN1 MT0W MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 19: ...17 MOF 18HFN1 MU0W...
Страница 20: ...18 MOG 24HFN1 MT0W...
Страница 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited...
Страница 53: ...51 Take the 9k model as example P U P V...
Страница 54: ...52 P W N U...
Страница 55: ...53 N V N W...