33
frequency will not be limited by T2.
----T2>60°C(140°F), the compressor will stop
and restart when T2<48°C(118.4°F).
8.4.4 Auto-mode
This mode can be chosen with remote
controller and the setting temperature can be
changed between 17°C(62.6°F)~30°C(86°F).
In auto mode, the machine will choose cooling,
heating or fan-
only mode according to ΔT
(ΔT =T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
1°C(33.8°F)
Cooling
-1°C(30.2°F)
<ΔT≤1°C(33.8°F)
Fan-only
ΔT≤-1°C(30.2°F)
Heating
Indoor fan will run at auto fan of the relevant
mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will keep stopping
for 15 minutes and then choose mode
according to T1-Ts.
If the setting temperature is modified, the
machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at breeze and
can’t be changed. The louver angle is the same
as in cooling mode.
8.4.5.2 Compressor running rules
T1-Ts
F3
F2
F1
F1
2.5¡ã
C(36.5¡ã
F)
2.0¡ã
C(35.6¡ã
F)
1.5¡ã
C(34.7¡ã
F)
1.0¡ã
C(33.8¡ã
F)
0.5¡ã
C(32.9¡ã
F)
0.0¡ã
C(32.0¡ã
F)
8.4.5.3 Low indoor room temperature protection
In drying mode, if room temperature is lower
than 10°C(50°F), the compressor will stop and
not resume until room temperature exceeds
12°C(53.6°F).
8.4.5.4 Evaporator anti-freezing protection,
condenser high temperature protection and
outdoor unit frequency limit are active and the
same as that in cooling mode.
8.4.5.5 The outdoor fan operates the same as
in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
When the machine is off, pressing the touch
button will carry the machine to forced auto
mode. If pressing the button once again within
5 seconds, the machine will turn into forced
cooling mode.
In forced auto, forced cooling or any other
operation mode, pressing touch button will turn
off the machine.
8.4.6.2 In forced operation mode, all general
protections and remote control are available.
8.4.6.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and
indoor fan runs as breeze. After running for 30
minutes. the machine will turn to auto mode as
24°C(75.2°F) setting temperature.
Forced auto mode:
The action of forced auto mode is the same as
normal auto mode with 24°C(75.2°F) setting
temperature.
8.4.7 Timer function
8.4.7.1 Timing range is 24 hours.
8.4.7.2 Timer on. The machine will turn on
automatically when reaching the setting time.
8.4.7.3 Timer off. The machine will turn off
automatically when reaching the setting time.
8.4.7.4 Timer on/off. The machine will turn on
automatica
lly when reaching the setting “on”
time, and then turn off automatically when
reaching the setting “off” time.
8.4.7.5 Timer off/on. The machine will turn off
automatically when reaching the setting “off”
time, and then turn on automatically when
reaching
the setting “on” time.
8.4.7.6 The timer function will not change the
AC current operation mode. Suppose AC is off
Содержание Mono 3D
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MS11M 09HRFN1 MW0W MS11M 12HRFN1 MV0W MS11M 18HRFN1 MU0W...
Страница 15: ...13 MS11M 24HRDN1 MT0W...
Страница 16: ...14 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 17: ...15 MOF 18HFN1 MU0W...
Страница 18: ...16 MOG 24HFN1 MT0W MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 19: ...17 MOF 18HFN1 MU0W...
Страница 20: ...18 MOG 24HFN1 MT0W...
Страница 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited...
Страница 53: ...51 Take the 9k model as example P U P V...
Страница 54: ...52 P W N U...
Страница 55: ...53 N V N W...