34
now, it will not start up firstly after setting the
“timer off” function. And when reaching the
setting time, the timer LED will be off and the
AC running mode has not been changed.
8.4.7.7 The setting time is relative time.
8.4.8 Sleep function mode
8.4.8.1 Operation time in sleep mode is 7 hours.
After 7 hours the AC quits this mode and turns
off.
8.4.8.2. Operation process in sleep mode is as
follow:
When cooling, the setting temperature rises
1°C(33.8°F) (be lower than 30°C(86°F)) every
one hour, 2 hours later the setting temperature
stops rising and indoor fan is fixed as low
speed.
When heating, the setting temperature
decreases 1°C(33.8°F) (be higher than
17°C(62.6°F)) every one hour, 2 hours later the
setting temperature stops rising and indoor fan
is fixed as low speed. (Anti-cold wind function
has the priority)
8.4.8.3 Timer setting is available
8.4.8.4 When user uses timer off function in
sleep mode (or sleep function in timer off mode),
if the timing is less than 7 hours, sleep function
will be cancelled when reaching the setting time.
If the timing is more than 7 hours, the machine
will not stop until reaches the setting time in
sleep mode.
8.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart
function, which is carried out through an
auto-restart module. In case of a sudden power
failure, the module memorizes the setting
conditions before the power failure. The unit will
resume the previous operation setting (not
including swing function) automatically after 3
minutes when power returns.
If the memorization condition is forced cooling
mode, the unit will run in cooling mode for 30
minutes and turn to auto mode as 24°C(75.2°F)
setting temp.
If AC is off before power off and AC is required
to start up now, the compressor will have 1
minute delay when power on. Other conditions,
the compressor will have 3 minutes delay when
restarts.
8.4.10 Follow me
1) If the indoor PCB receives the signal which
results from pressing the FOLLOW ME button
on remote controller, the buzzer will emit a
sound and this indicates the follow me function
is initiated. But when the indoor PCB receives
signal which sent from remote controller every
3 minutes, the buzzer will not respond. When
the unit is running with follow me function, the
PCB will control the unit according to the
temperature from follow me signal, and the
temperature collection function of room
temperature sensor will be shielded, but the
error detective function of room temperature
sensor will be still valid.
2) When the follow me function is available,
the PCB will control the unit according to the
room temperature from the remote controller
and the setting temperature.
3) The PCB will take action to the mode
change information from remote controller
signal, but it will not affected by the setting
temperature.
4) When the unit is running with follow me
function, if the PCB doesn’t receive any signal
from remote controller for 7 minutes or pressing
FOLLOW ME button again, the follow me
function will be turned off automatically, and the
temperature will control the unit according to
the room temperature detected from its own
room temperature sensor and setting
temperature.
8.4.11 Self clean
For heat pump models which are provided with
this function, after running in cooling or drying
mode, if the user press “Self Clean” button on
remote controller, firstly, indoor unit runs in fan
only mode for a while, then low heat operation
and finally runs in fan only again. This function
can keep the inside of indoor unit dry and
prevent breeding of mold.
8.4.12 Refrigerant Leakage Detection
With this new technology, the display area will
Содержание Mono 3D
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MS11M 09HRFN1 MW0W MS11M 12HRFN1 MV0W MS11M 18HRFN1 MU0W...
Страница 15: ...13 MS11M 24HRDN1 MT0W...
Страница 16: ...14 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 17: ...15 MOF 18HFN1 MU0W...
Страница 18: ...16 MOG 24HFN1 MT0W MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 19: ...17 MOF 18HFN1 MU0W...
Страница 20: ...18 MOG 24HFN1 MT0W...
Страница 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited...
Страница 53: ...51 Take the 9k model as example P U P V...
Страница 54: ...52 P W N U...
Страница 55: ...53 N V N W...