9.3.9 High temperature protection of compressor top diagnosis and solution(P2)
Error Code
P2
Malfunction decision
conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Trouble shooting:
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the unit can start
normally.
No
Check if the refrigerant
charge volume is normal?
Recharge the correct
refrigerant volume.
Refrigerant system is blocked, such
as capillary or welded point of pipes.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
No
Содержание Mono 3D
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MS11M 09HRFN1 MW0W MS11M 12HRFN1 MV0W MS11M 18HRFN1 MU0W...
Страница 15: ...13 MS11M 24HRDN1 MT0W...
Страница 16: ...14 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 17: ...15 MOF 18HFN1 MU0W...
Страница 18: ...16 MOG 24HFN1 MT0W MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 19: ...17 MOF 18HFN1 MU0W...
Страница 20: ...18 MOG 24HFN1 MT0W...
Страница 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited...
Страница 53: ...51 Take the 9k model as example P U P V...
Страница 54: ...52 P W N U...
Страница 55: ...53 N V N W...