9.3.2 Indoor / outdoor
unit’s communication diagnosis and solution(E1)
Error Code
E1
Malfunction decision
conditions
Indoor unit does not receive the feedback from outdoor unit during
110
seconds and this condition happens four times continuously.
Supposed causes
●
Wiring mistake
●
Indoor or outdoor PCB faulty
Trouble shooting:
Yes
Yes
Measure Vs, is it moving alternately
with positive value?
(Vs is the voltage between L2 and S
of outdoor unit. Connect the red pin of
multimeter with L2 port, black pin with
S port)
Yes
Power off, then turn on the unit 5 seconds
later(reconnect the power wire).Is the error
still displaying after several minutes?
No
Replace the outdoor main PCB.
Power on. Is the error extinguished?
Check all the wiring with indoor units.
Is the wiring to the indoor main PCB
connected correctly?
Replace the indoor main PCB.
Yes
Replace the outdoor main PCB.
No
Check all the wiring with outdoor
u n i t s . Is the wiring to the outdoor
m a i n PCB connect e d correctly? I s
the reactor connected well?
Power on. Is the error extinguished?
Replace the indoor main PCB.
No
Yes
M e a s u r e t h e r e s i s t a n c e o f t h e
reactor(The one without capacitor).
If it is zero ,follow the below step. If
not, replace a new reactor.
Содержание Mono 3D
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MS11M 09HRFN1 MW0W MS11M 12HRFN1 MV0W MS11M 18HRFN1 MU0W...
Страница 15: ...13 MS11M 24HRDN1 MT0W...
Страница 16: ...14 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 17: ...15 MOF 18HFN1 MU0W...
Страница 18: ...16 MOG 24HFN1 MT0W MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Страница 19: ...17 MOF 18HFN1 MU0W...
Страница 20: ...18 MOG 24HFN1 MT0W...
Страница 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited...
Страница 53: ...51 Take the 9k model as example P U P V...
Страница 54: ...52 P W N U...
Страница 55: ...53 N V N W...