Floor Standing MFM
DM16-01.01.25en
Service manual
44
10.1.2 LEDs for the indication of outdoor trouble (only for 48K-50K)
Their codes are listed in the following table:
LED2(green)
LED3(yellow)
LED4(red)
Contents
On
Off
Off
OK
Off
On
Off
Standby
Off
Off
Flash
Lack of phase
Off
Flash
Off
Phase sequence error
Off
Flash
Flash
Communication malfunction between indoor unit
and outdoor unit
Off
Off
On
Open- or short-circuit of T3 temperature sensor
Flash
Off
Off
Open- or short-circuit of T4 temperature sensor
On
Off
On
Temperature protection of compressor discharge
Flash
Flash
Off
High pressure protection
Flash
Off
Flash
Low pressure protection
Off
Flash
On
Overload of current
Flash
Flash
On
High temperature protection of condenser
Flash
Flash
Flash
Fan jump selection error