9.3.1.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/low/auto. And the anti-cold wind
function has the priority.
Auto fan action:
T1-Ts
Low
High
9.3.1.4 Defrost (only available to heating mode)
---Defrosting Conditions
Starting Of Defrosting Condition (meet one of the following is ok):
(1)Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to
40 minutes, then consecutive 3 minutes less than -5 degrees (Just for the AC is turn on ,
whether or not the heating mode the temperature was detected, start to statistical time when reach
the temperature condition . Shut down or defrosting calculate time again).
(2) Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to
60 minutes, then consecutive 3 minutes less than -4 degrees (Just for the AC is turn on ,
whether or not the heating mode the temperature was detected, start to statistical time when reach
the temperature condition . Shut down or defrosting calculate time again).
(3) Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to
80 minutes, then consecutive 3 minutes less than -2 degrees (Just for the AC is turn on ,
whether or not the heating mode the temperature was detected, start to statistical time when reach
the temperature condition . Shut down or defrosting calculate time again).
(4) Under evaporator high temperature protection, the accumulated time when outdoor fan motor is
off and compressor is on reaches up to over 90 minutes .( Shut down or defrosting or T3 is over
15°C, calculate time again.)
--- Defrosting Action
Four-way valve, indoor fan, outdoor fan are shut down. Compressor keeps on.
Содержание MFM-24ARN1-Q
Страница 12: ...Floor Standing MFM DM16 01 01 25en Service manual 12 5 2 MFM 48ARN1 R Indoor unit Outdoor unit MOU 48HN1 RB6W...
Страница 13: ...DM16 01 01 25en Floor Standing MFM 13 Service manual 5 3 MFM 60ARN1 R Indoor unit Outdoor unit MOUL 60HN1 R...
Страница 34: ...Floor Standing MFM DM16 01 01 25en Service manual 34 7 2 Control Panel Control Buttons and Functions...
Страница 50: ...Floor Standing MFM DM16 01 01 25en Service manual 50 10 2 9 Overload of current 1...
Страница 52: ...Floor Standing MFM DM16 01 01 25en Service manual 52 10 2 11 Refrigerant Leakage Detection...
Страница 53: ...DM16 01 01 25en Floor Standing MFM 53 Service manual 10 2 12 Temperature protection of compressor discharge...