9.3.2.5 Condenser high temperature T3 protection
T3
Off
On
When high condenser temp. T3 is more than setting value,for setting time the compressor will stop.
9.3.3 Dehumidifying Mode
9.3.3.1 Indoor fan speed is low.
9.3.3.2 Four-way valve is closed, the compressor and outdoor fan will operate the same as in cooling mode.
9.3.4 Auto Mode
9.3.4.1. Under auto mode, the indoor fan is set to be auto and the temperature is 24°C.
9.3.4.2 When entering auto mode, the heating, fan only or cooling operation will be automatically chosen according
to the room temperature T1 and the set temperature Ts.
T1-Ts
Cooling
Heating*
Fan only
9.3.4.3. If certain condition is met, then the corresponding protective function will be executed.
9.3.5 Fan Only Mode
9.3.5.1 Temperature setting function is disabled, and no setting temperature is displayed.
9.3.5.2 Under this mode, four-way valve, compressor and outdoor fan are shut down.
9.3.5.3 High/Low/Auto fan can be switched over through manual control. Auto fan will be controlled in line with
cooling auto fan with temperature set to be 24°C.
Содержание MFM-24ARN1-Q
Страница 12: ...Floor Standing MFM DM16 01 01 25en Service manual 12 5 2 MFM 48ARN1 R Indoor unit Outdoor unit MOU 48HN1 RB6W...
Страница 13: ...DM16 01 01 25en Floor Standing MFM 13 Service manual 5 3 MFM 60ARN1 R Indoor unit Outdoor unit MOUL 60HN1 R...
Страница 34: ...Floor Standing MFM DM16 01 01 25en Service manual 34 7 2 Control Panel Control Buttons and Functions...
Страница 50: ...Floor Standing MFM DM16 01 01 25en Service manual 50 10 2 9 Overload of current 1...
Страница 52: ...Floor Standing MFM DM16 01 01 25en Service manual 52 10 2 11 Refrigerant Leakage Detection...
Страница 53: ...DM16 01 01 25en Floor Standing MFM 53 Service manual 10 2 12 Temperature protection of compressor discharge...