--- Ending Of Defrosting Condition (meet one of the following is ok):
(1)Time of defrosting lasts 10 minutes.
(2) Temperature of outdoor coil T3 is up to 8°C and continues to 80 seconds.
(3) Temperature of outdoor coil T3 is up to 15°C.
9.3.1.5 High evaporator coil temp.T2 protection:
9.3.2 Cooling Mode
9.3.2.1 Four-way valve is closed.
If four-way valve is open before the machine enters cooling mode, then four-way valve will be
closed at the first time, the compressor starts under the cooling mode.
9.3.2.2 Compressor and outdoor fan running rules
Once the compressor starts up, it will follow the below rules:
Содержание MFM-24ARN1-Q