24
Replace the sensor
Display LED
STATUS
E1
No 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
Display LED
STATUS
E2
No 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
Display LED
STATUS
E3
No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes