8 Electronic control function 

 

8.1 Protection 

1.    3 minutes delay at restart for compressor. 
2.    Temperature protection of compressor top, compressor stops when the temp. of top of 
compressor is more than 120

, compressor runs when the temp. of top of compressor is 

less than 105

3.  When AC voltage 

 270V for 30 seconds, Outdoor Unit stops operation and alarms. 

When AC voltage 

 260V for 30 seconds, outdoor unit resumes operation. 

4.  Inverter module protection, Inverter module Protection itself has a protection function 
against current, voltage and temperature. 
5.  Sensor protection at open circuit and breaking disconnection. 
6.    Fan Speed is out of control. When Indoor Fan Speed is too high (higher than High 
Fan+300RPM) or too low (lower than 400RPM), the unit stops and LED displays failure 
information and can’t return to normal operation automatically.

 

 

7.    Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit 
stops and LED displays failure information and can’t return to normal operation 
automatically

 

8.  Current protection: When the current is more than 25A, the compressor stops. 
9.    Outdoor condenser high temperature protection: Under cooling mode, if T3>65

 for 3 

minutes, the compressor will stop. When T3<52

, the protection is not valid.   

10.    Outdoor low temperature protection: If the outdoor temperature is lower than -15

 

for 1hour, the compressor and fan motor will stop. If the outdoor temperature is higher than 
-12

  for 10 minutes and the compressor stops operation for 1h, or the outdoor 

temperature is higher than 5

  for 10 minutes, then restart and enter into the prior 

operation mode. 
11.    Compressor pre-heating function: When the outdoor temperature is lower than 3

 

and the compressor stops operation for more than 3 hours, or the outdoor temperature is 
lower than 3

  and the power is just put on, the compressor enters into pre-heating 

condition. When outdoor temp. is more than 5

  or user operate it, pre-heating condition 

will finish. 

 
8.2  Operating mode  
8.2.1  Cooling mode 

1.Indoor fan keeps running, fan speed can be set in high/mid/low/ Auto:   
2.Auto fan at cooling mode: (T=Indoor Temp.-Setting Temp.) 

 

Condition 

Indoor fan speed 

T<1.5

 

Low 

1.5

<T<4

 

Mid. 

Room temp. up 

 

T>4

 

High 

T> 3

 

High 

1

<T<3

 

Mid. 

Room temp. down 

T<1

 

Low 

3.Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) 

Downloaded from AC-Manual.com Manuals

Содержание M2OA-18HRIN1

Страница 1: ...MULTI SPLIT TYPE HEAT PUMP AIR CONDITIONERS Technical service manual 2006 R410A Vertu Inverter multi Series Indoor Models MSV1I 09HRDN1 MSV1I 12HRDN1 Outdoor Models M2OA 18HRIN1 M3OA 27HRIN1 M40A 27HR...

Страница 2: ...cle diagram 4 Operation temperature limits 5 Indoor units combination 6 Wiring diagram 7 Wiring connection 8 Electric control functions 9 Troubleshooting Annex 1 Characteristic of temp sensor Annex 2...

Страница 3: ...ction at cooling mode 1 4 Anti cold air function at heating mode 1 5 Auto defrosting 1 6 Outdoor electric current protection 1 7 Temperature protection of the outdoor compressor top 1 8 Error self dia...

Страница 4: ...2 Dimensions 2 1 Indoor unit 2 2 Outdoor unit a Outdoor unit M2OA 18HRIN1 M3OA 27HRIN1 Dimension Mode W H D 9K 795 270 165 12K 845 286 165 Downloaded from AC Manual com Manuals...

Страница 5: ...5 335 845 b Outdoor unit M4OA 27HRIN1 Downloaded from AC Manual com Manuals...

Страница 6: ...valve EXV C Gas valve C Liquid valve A Gas valve D EXV C Capillary C Filter C Liquid valve D Indoor pipe out temp seneor D Coil temp sensor 3 2 Refrigeration circuit drawing of inverter trinary type L...

Страница 7: ...Capillary A Capillary B Exhaust temp sensor Indoor pipe out temp seneor A Indoor pipe out temp seneor B Filter A Filter B Outdoor Unit Main Capillary Check Valve Coil temp sensor 4 Operation Temperatu...

Страница 8: ...u h 9000 Btu h 12000Btu h 7000Btu h 9000 Btu h 7000Btu h 12000Btu h 9000Btu h 9000 Btu h 9000Btu h 12000Btu h 12000Btu h 12000Btu h 12000Btu h 18000Btu h 9000Btu h 18000Btu h 7000Btu h 18000Btu h 7000...

Страница 9: ...00Btu h 2 9000 Btu h 2 7000Btu h 2 9000 Btu h 12000 Btu h 7000Btu h 3 9000 Btu h 7000Btu h 3 12000 Btu h 7000Btu h 3 18000 Btu h 7000Btu h 4 9000Btu h 2 7000 Btu h 12000 Btu h 9000Btu h 3 7000 Btu h 9...

Страница 10: ...10 6 Wiring Diagram 6 1 Indoor unit 6 2 Outdoor unit M2OA 18HRIN1 Downloaded from AC Manual com Manuals...

Страница 11: ...11 6 3 Outdoor unit M3OA 27HRIN1 Downloaded from AC Manual com Manuals...

Страница 12: ...12 6 4 Outdoor unit M4OA 27HRIN1 Downloaded from AC Manual com Manuals...

Страница 13: ...ounding 1 0 Neoprene YZW300 500V Remark The connection wire between indoor unit and outdoor unit is standard And it is packaged in the indoor unit 7 2 Connection wire drawing 20 10 2 Neoprene YZW300 5...

Страница 14: ...than 25A the compressor stops 9 Outdoor condenser high temperature protection Under cooling mode if T3 65 for 3 minutes the compressor will stop When T3 52 the protection is not valid 10 Outdoor low t...

Страница 15: ...heating mode Indoor Fan can be set at HIGH MID LOW AUTO by using a remote controller but Anti cold wind function prevails Anti cold wind control function at heating mode Condition T Indoor exchanger...

Страница 16: ...cording to anti cold wind function in heating mode 4 Automatic operation mode The air conditioner automatically selects one of the following operation modes cooling heating or fan only according to th...

Страница 17: ...er than off time first turn off the A C it will be automatically on at set time and later be off at the set time then unit turns on at set time 5 Timer off on function off time is earlier than on time...

Страница 18: ...O indicator This indicator illuminates when the air conditioner is in AUTO operation 8 9 3 TIMER indicator This indicator illuminates when TIMER is set ON OFF 8 9 4 CLEAN AIR indication lamp Lights up...

Страница 19: ...vised capacity fan state No 1 evaporator pipe temp No 2 evaporator pipe temp No 3 evaporator pipe temp No 4 evaporator pipe temp outdoor pipe temp Outdoor temp discharge gas temp current of outdoor un...

Страница 20: ...ent temp rise 27 Low speed 25 High speed Ambient temp decline 25 Low speed When heating 14 Low speed Ambient temp rise 14 High speed 12 Low speed Ambient temp decline 12 High speed 8 13 Oil return fun...

Страница 21: ...upply electricity power still are kept in capacitors do not forget to discharge the electricity power in capacitor The value of resistance is about 1500 ohm to 2000 ohm Resistance The voltage in P3 an...

Страница 22: ...lanation E0 EEPROM error E1 No 1 Indoor units pipe temp sensor or connector of pipe temp sensor is defective E2 No 2 Indoor units pipe temp sensor or connector of pipe temp sensor is defective E3 No 3...

Страница 23: ...e shooting Display LED STATUS E0 EEPROM error Yes Temporarily turn off the power supply and turn it on again after 1 minute Does the trouble occur again Replace the indoor PCB Downloaded from AC Manua...

Страница 24: ...p sensor is defective Is connection to connector of pipe temp sensor good Check the resistance of the temp sensor according to Annex 1 Repair connector No Yes Replace the sensor Is connection to conne...

Страница 25: ...e temp sensor according to Annex 1 Repair connector No Yes Replace the sensor Yes Check the voltage of power supply if the voltage is about 220V turn off the power supply to indoor unit and turn it on...

Страница 26: ...d connection or defective when the voltage in outdoor is abnormal P3 and P4 310V DC P5 and P6 310V DC No Yes No Check the PC817 PC851 at Indoor main PCB and outdoor main board Normally Input voltage 5...

Страница 27: ...volume normal Gas charging Is abnormality the same after gas charging Refrigerant system such as clogging of capillary clogging of pipe etc Is protector on the top of compressor normal Normally the re...

Страница 28: ...door unit only Does the compressor start after 3 minutes Does the trouble occur again after compressor running some time No Yes No The compressor is defective Check the refrigerant circulation volume...

Страница 29: ...ly P N 1 0M P U 2 0M P V 2 0M P W 2 0M N W 1 0M N U 1 0M N V 1 0M Check compressor 1 Turn on the unit in cooling or heating in different season use a frequency meter to test the frequency in one of th...

Страница 30: ...ction When outdoor pipe temp is more than 65 C the unit will stop and unit runs again when outdoor pipe temp is less than 52 C Is the outdoor temp lower than 15 C Is the outdoor temp sensor right acco...

Страница 31: ...6 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58 2 5397 5 26 8778 32 7 2946 59 2 4468 6...

Страница 32: ...0V AC V W 60 150V AC P N DC 310V c Photo couple PC817 PC851 Control side 5V AC side 24V AC d S terminal and N changeable from 0 24V 2 Check the Diode Bridge component In wiring diagram rectifier Remar...

Отзывы: