28
Display LED
STATUS
P3
Compressor current protection
Check the resistance of compressor, normally
U and V is 0.6 ohm
U and W is 0.6 ohm
V and W is 0.6 ohm
Turn one indoor unit only, Does the compressor start after
3 minutes?
Does the trouble occur again after compressor
running some time?
No
Yes
No
The compressor is defective
Check the refrigerant circulation volume and pressure
No
The compressor is defective
Yes
If refrigerant circulation volume and pressure is OK, change the outdoor main PCB.