15
Evaporator
Temp.
Compressor
T< 4
℃
Off
T > 8
℃
On
8.2.2 Dehumidifying mode
1.The indoor fan is fixed in low speed
2. Low room temperature protection:
When room temperature decreases to below 10
℃
, indoor fan stop, when room
temperature restores to over 12
℃
, indoor fan start.
3.
At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the
same as that of cooling mode.
8.2.3 Heating mode
1. Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function
prevails.
Anti-cold wind control function at heating mode
Condition
T= Indoor exchanger
temp.
Indoor fan speed
T<34
℃
Off
34
℃
<T<37
℃
Breeze
37
℃
<T<44
℃
Low
speed
Indoor exchanger temp.
up
T> 44
℃
Setting fan speed
T> 38
℃
Setting fan speed
33
℃
<T<38
℃
Low
speed
24
℃
<T<33
℃
Breeze
Indoor exchanger temp.
down
T<24
℃
Off
Auto wind at heating mode
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<1.5
℃
High
1.5
℃
<T<2.5
℃
Mid.
Room temp. up
T>2.5
℃
Low
T<1.0
℃
High
1.0
℃
<T<2.0
℃
Mid.
Room temp. down
T>2.0
℃
Low
Downloaded from AC-Manual.com Manuals
Содержание M2OA-18HRIN1
Страница 5: ...5 335 845 b Outdoor unit M4OA 27HRIN1 Downloaded from AC Manual com Manuals...
Страница 10: ...10 6 Wiring Diagram 6 1 Indoor unit 6 2 Outdoor unit M2OA 18HRIN1 Downloaded from AC Manual com Manuals...
Страница 11: ...11 6 3 Outdoor unit M3OA 27HRIN1 Downloaded from AC Manual com Manuals...
Страница 12: ...12 6 4 Outdoor unit M4OA 27HRIN1 Downloaded from AC Manual com Manuals...