![Midea KJRM-120H2/BMWKO-E Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/midea/kjrm-120h2-bmwko-e/kjrm-120h2-bmwko-e_owners-manual_1790916054.webp)
50
Defrost
282+(Unit
Address)*100
0:OFF 1:ON
Anti-freezing
electric heater
283+(Unit
Address)*100
0:OFF 1:ON
Remote control
state
284+(Unit
Address)*100
0:OFF 1:ON
Only available on host unit
Pump group
status
286+(Unit
Address)*100
1: Multiple pump
0: Single pump
Tsafe
289+(Unit
Address)*100
Uints: 1°C(Available for Only Cool
& Free Cooling)
MainBoard
Software Version
292+(Unit
Address)*100
Mainboard software version (0
stands for the unit has no version
data)
MainBoard
EEPROM Version
293+(Unit
Address)*100
Mainboard software version (0
stands for the unit has no version
data)
Note: Unit Address stands for machine address 0-15, 0 stands for host 0.