![Midea KJRM-120H2/BMWKO-E Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/midea/kjrm-120h2-bmwko-e/kjrm-120h2-bmwko-e_owners-manual_1790916052.webp)
48
Addresses below can be used as 03(Read Holding Registers)
Data Content
Address of Register Notes
Running Mode
240+(Unit
Address)*100
1: OFF
2: Cooling Mode
3: Heating Mode
4: DHW Mode
Current silent
mode
241+(Unit
Address)*100
1: Standard mode
2: Silent mode
3: Super silent mode
4: Night silent mode 1
5: Night silent mode 2
6: Night silent mode 3
7: Night silent mode 4
DHW Set
Temperature T5S
242+(Unit
Address)*100
Uints: 1°C
Single pump: All units have same
T5S
Multiple pump: All units have
individual T5S
Unit inlet water
temperature
244+(Unit
Address)*100
Uints: 1°C
Unit outlet water
temperature
245+(Unit
Address)*100
Uints: 1°C
Total outlet water
temperature
246+(Unit
Address)*100
Uints: 1°C
Only available on host unit
Outdoor ambient
temperature
247+(Unit
Address)*100
Uints: 1°C