Parallel units setting:
Select "SET PARALLEL UNIT" and press "
" to entry. Display as follows:
SET PAPALLEL UNIT
TIM_CAP_ADJ
TW_HEAT_DIFF
180
OK
RATIO_COOL_FIRST
RATIO_HEAT_FIRST
2
0
S
50
%
TW_COOL_DIFF
2
°C
°C
%
Press " ▲ " or " ▼ " to select item to be set and press " ◄ " or " ► " to set value. Press
"
" to confirm. Back to homepage if there is no operation within 60s.
Detailed setup information:
Parameter
Setting range
Tim_Cap_Adj
60s
∽
360s
Tw_Cool_diff
1
∽
5°C
Tw_Heat_diff
1
∽
5°C
Ratio_cool_first
5
∽
100%
Ratio_heat_first
5
∽
100%
Unit protection setting:
Select "SET UNIT PROTECTION" and press "
" to entry. Display as follows:
SET UNIT PROTECTION
T_DIFF_PRO
OK
2
°C
TWI_O ABNORMAL
12
°C