![Midea KJRM-120H2/BMWKO-E Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/midea/kjrm-120h2-bmwko-e/kjrm-120h2-bmwko-e_owners-manual_1790916049.webp)
45
Silent Mode
100
1:Standard mode
2:Silent mode
3:Night silent mode 1
4:Night silent mode 2
5:Night silent mode 3
6:Night silent mode 4
7:Super silent mode
DOUBLE
SETPOINT
101
Enable/Disable 1/0
SETPOINT
COOL_1
102
Only Cool & Free Cooling :
(Max(-8, TSafe)°C ~20°C)
Normal Heat Pump (TwsMin°C ~20°C)
SETPOINT
COOL_2
103
Only Cool & Free Cooling :
(Max(-8, TSafe)°C ~20°C)
Normal Heat Pump : (TwsMin°C ~20°C)
SETPOINT
HEAT_1
104
(25~55°C)
SETPOINT
HEAT_2
105
(25~55°C)
DHW SWITCH
115
1: Enable
0: Disable
(Available for single pump)
For no DHW machine, any write operation
on this register is invalid.
Modbus Control
switch
138
1: Enable
0: Disable
Содержание KJRM-120H2/BMWKO-E