24
Under "FORCED PUMP OPEN" page, press " ▲ " or " ▼ " to select item and press " ◄ " or
" ► " to set value. Press "
" to confirm or " " to back. If the unit at that address is ON,
the pump cannot be controlled by the wired controlled. Display as above.
Under "INV PUMP OPEN" page, press " ▲ " or " ▼ " to select item and press " ◄ " or " ► "
to set value. Press "
" to confirm or " " to back.
INV PUMP SETTING
SWITCH ON THE
PUMP
OK
SELECT ADDRESS
07 #
NO
RATIO PUMP
100 #
Note: Can only be set under a single pump ,The setting range of RATIO-PUMP is 30%-
100%. It should ensure its flow meet the requirement of whole unit, otherwise the unit may
be damaged.
Under "PUMP CONTROL" page, press " ▲ " or " ▼ " to select item and press " ◄ " or " ► "
to set value. Press "
" to confirm or " " to back.
PUMP ON/OFF TIME
PUMP OFF TIME
OK
PUMP ON TIME
05
MIN
05 MIN
Parameter setting requirements are as follows:
Set range
Default value
Adjustment range
PUMP ON TIME
5~60min
5
5
PUMP OFF TIME
0~60min
0
5